Kidde 151FE1 Installation, Operation & Maintenance Manual Download Page 11

06-235793-001

December 2001

Scorpio

7

TECHNICAL SPECIFICATIONS

Input Power:

120 Vac, 50/60 Hz  0.5 A max.

240 Vac, 50/60 Hz  0.25 A max.

An impedance of 25K ohms from any field wiring terminal
to ground except AC input power and relay outputs will
cause a ground fault condition.

Panel 24 VDC Power Requirements:

Standby Current: 35mA

Alarm Current: 200mA

Auxiliary Power:

24 Vdc at 0.25A in alarm only

Output Circuit:

One Style-Y signal circuit, 10K ohm EOL.

Rated at 24 Vdc 0.5 A (max)

Open circuit fault impedance: 13.5K ohms

Short circuit fault impedance: 4.5K ohms

When programmed for two-zone operation, pulses on first
alarm, steady output on second alarm.

Relay Outputs:

Alarm 1 relay (activates on 1st zone in alarm)

Alarm 2 relay (activates on 2nd zone in alarm or
start of release)

Note:

When set up is for a single zone release, S1=ON,
Alarm 1 and Alarm 2 relays will both activate on
first alarm.

Trouble relay (normally energized)

All are Form C, rated 2A @ 250 Vac/30 Vdc

Note:

For ULC installations, the form C relays are rated
for 120 V AC (150 V max to ground).

Release Output, Solenoid Style

Output circuit capable of activating 2 of the following con-
trol heads P/Ns:

48650001

890181

899175

Output held ON for 90 seconds. Circuit is power limited
and supervised on terminals 28-31.

Open circuit fault impedance: 1.7K ohms

UL Compatibility Identifier Number: 

     C30FE1

Two Detection Circuits:

Output voltage: 17.3 - 26.0 Vdc

Max. number of 2 wire smoke detectors per circuit: 15

Maximum line resistance: 50 Ohms

Operation: Style B, 10K ohm EOL.

See Table 1 for 2-wire detector compatibility

Open curcuit fault impedance: 22K ohms

Auxiliary Inputs:

Supervisory Input, Style B, 10K ohm EOL.

Manual Release Input, Style B, 10K ohm EOL.

Abort Input, Style B, 10K ohm EOL.

Open circuit fault impedance for Abort, Supervisory
and Manual release: 22K ohms

Isolation Switch:

Disconnects the release output. Available by cutting jump-
ers W1 and W2.

Standby Batteries:

Requires (2) 12 Vdc 1.2A-H sealed lead acid batteries for
24 hour standby operation/5 minute alarm operation at
maximum rated load. Order separately.

Battery Charger Output:

Nominal Standby Load: 35 mA

Maximum Charging Current 0.48 A

Time Delay to Discharge:

0, 10, 20, 30, 40, 50, or 60 seconds field selectable.

Dimensions (nominal):

  13.25”H x 11.0”W x 2.30”D

ORDERING INFORMATION

DESCRIPTION

PART NO.

Scorpio Control Panel

84-232000-102

Above panel (240 Vac input)

84-232000-104

(1) Battery 12 Vdc 1.2 A-H

06-115915-020

Accessory Kit (50 10K EOL resistors)

06-129520-001

Extra Operating Instruction Sheet

06-235883-001

Spare Scorpio Circuit Board

06-129800-002

Extra Scorpio Key

06-118013-001

Canadian Scorpio

84-232000-202

Canadian Scorpio (240 Vac Input)

84-232000-204

firealarmresources.com

Summary of Contents for 151FE1

Page 1: ...Scorpio Fire Control Panel Installation Operation Maintenance Manual December 2001 TM Fire Systems P N 06 235793 001 UL Listing File No S2422 firealarmresources com...

Page 2: ...firealarmresources com...

Page 3: ...not interfere with battery and printed circuit board location Do not over tighten screw terminals over tightening may damage threads resulting in reduced terminal contact pressure and difficult with s...

Page 4: ...y trained distributors technicians The entire manual should be read and fully understood prior to installation TEST EQUIPMENT Make certain test equipment is in good operating condition Do not touch li...

Page 5: ...first alarm and is a steady output on second alarm An independent form C dry con tact is associated with each of the two alarm levels when programmed for two zone release Alarm Relay 2 may also be con...

Page 6: ...instructions LAMP TEST Use the following steps to test all LEDs on the Control Panel 1 Hold the RESET Switch down All LEDs should light up 2 Release the RESET Switch All LEDs should return to Normal T...

Page 7: ...nction S2 6 OFF Disables the abort function S2 7 S2 8 Switches 2 7 and 2 8 allows the installer to pro gram the desiredAbort mode for the installation There are three modes of Abort as explained in a...

Page 8: ...RY POWER Batteries provide 24 hour standby supervision plus 5 minute alarm load at the end of that time contingent upon detection and output limitations stated herein Panel load ing and battery standb...

Page 9: ...002 W1 W2 S4 F F O ON ISOLATE BATT XFMR ON S2 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 NO 16 C 17 NC 18 NO 19 C 20 NC 21 NO 22 C 23 NC 24 25 26 27 28 29 30 31 1 1 1 1 1 2 2 1 ALARM 1 ALARM...

Page 10: ...etracted or SET position Electric control head P N 48650001 is designed for installation on a 487 or ECS series control head only Installation of this control head to any other device e g pressure ope...

Page 11: ...d on terminals 28 31 Open circuit fault impedance 1 7K ohms UL Compatibility Identifier Number C30FE1 Two Detection Circuits Output voltage 17 3 26 0 Vdc Max number of 2 wire smoke detectors per circu...

Page 12: ...December 2001 06 235793 001 Scorpio 8 THIS PAGE INTENTIONALLY LEFT BLANK firealarmresources com...

Page 13: ...RREV DATE 5 SYSTEM EQUIPMENT 6 PRIORITY OF COMMENT 7 USEREVALUATION MANUALIS qEXCELLENT qGOOD qFAIR qPOOR qCOMPLETE qINCOMPLETE 8 qPROBLEM qQUESTION qSUGGESTION qCOMMENT check one 9 RECOMMENDEDCHANGET...

Page 14: ...KIDDE FENWAL Inc 400 Main Street Ashland MA 01721 Attn Documentation Manager Place Stamp Here FOLD FOLD firealarmresources com...

Page 15: ...firealarmresources com...

Page 16: ...hat this product is free from defects in material and workmanship and it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twen...

Reviews: