February 2012
1-22
P/N 06-237058-001
1-14.2
Remote Devices Using RS485 Bus to MCB
The ARIES NET
Link
system’s Main Controller Board includes an RS485 bus which can communicate
with the following remote devices:
•
Remote LED Annunciator Module (R-LAM)
•
Remote Display Control Module (RDCM)
•
Model ATM-L Annunciator Driver Module
•
Model ATM-R Relay Driver Module
•
Fiber Optic Converter Module
The ARIES NET
Link
control unit supports the use of:
•
up to 16 LED Annunciator Modules
•
up to 15 Remote Display Control Modules
•
up to 16 ATM-L or ATM-R Driver Modules (or any combination of these modules)
Note:
The total number of remote devices cannot exceed 31 addresses. If an integrated LED
Annunciator is included in the ARIES NET
Link
front panel, the total number of remote
devices cannot exceed 30 addresses.
1-14.2.1
REMOTE LED ANNUNCIATOR MODULE
The Remote LED Annunciator Module (R-LAM) is an optional module which drives the display of
zone information and fits into the Remote Enclosure. The R-LAM provides 48 independently-
programmable microcontroller-controlled LEDs (red/yellow) with space available to place a label to
identify the event being annunciated. In addition, three system-level LED outputs are provided for
the following general conditions: Module Power, Trouble and Signal Silenced. Two system-level input
circuits for functional switches are reserved for Signal Silence and System Acknowledge/Self-Test
commands.
Note:
The file
LAM label template.doc
is provided on the ARIES NET
Link
User Disk, P/N
06-220289-002, to assist with customized labeling
.
Text for the labels can be entered into
preset form fields (up to two lines of text per window). Cut the strips with a scissors and slide
them into the LAM from the top, retaining the top tab for easy removal.
Refer to Figure 1-12 for an illustration of the Remote LED Annunciator Module. Refer to Appendix
E for an illustration of the integrated LED Annunciator used in Canadian Applications.
Figure 1-12. Remote LED Annunciator Module
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......