Operation
P/N 06-237058-001
4-13
February 2012
Figure 4-20. Typical Trouble Message Display
The following actions also occur when any trouble condition is reported:
•
The Trouble LED on the display flashes
•
The internal buzzer pulses
•
The Trouble Relay de-energizes to transfer the Trouble contacts
•
The trouble event is stored in the event log
•
The trouble message is transmitted to peripheral devices (such as Remote Display Control
Modules and Remote LED Annunciator Modules), if applicable
•
The trouble message is communicated via the RS232 ports.
•
Point- or group-specific and general trouble outputs activate, including previously silenced
outputs.
4-10.2.1
WHAT TO DO WHEN A TROUBLE OCCURS
Press the <SYSTEM ACKNOWLEDGE> Key to change the Trouble LED from flashing to steady and
to silence the internal buzzer.
It will be necessary to press the <SYSTEM ACKNOWLEDGE> Key once for each trouble report if
multiple unacknowledged trouble events are present and the global acknowledgment option has not
been selected.
Note:
Global Acknowledge for acknowledgement of multiple events is not ANSI/UL 864 compliant.
Each acknowledged trouble event (or block of events when the global acknowledgment option
is used) will disappear from the display. The display changes to indicate the next
unacknowledged trouble event in the case of multiple trouble events. The active troubles can
be manually displayed in order of occurrence using the <SCROLL> Key at this time, after all
trouble events have been acknowledged. A summary of the number of active trouble events will
be displayed as shown in Figure 4-21 at the conclusion of each manual scroll cycle.
Figure 4-21. Typical Message After Manual Trouble Scroll Cycle
A trouble event that occurs after all previous trouble events are acknowledged will re-initialize the
Trouble State as defined in Section 4-10.2.
L2:002 TROUBLE OPEN ON ALARM
FIRST FLOOR POWER ROOM
SLC
Loop
Number
2
Device
T
y
pe
w
ith
Fau
l
t
Device
-
Specific
Custom
M
essa
g
e
Device
Address
002
L1:001 TROUBLE OPEN ON ALARM
NEW ALARM INSTALLED
DISCHARGE-00 CNTDN-00 ABT-00 ALM-00
PREALM-00 AVCNTDN-00 SPV-000 TBL-002
Number
of
Troub
l
es
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......