General Information
06-237518-001
1-9
July 2018
1-5.2
IG-100 (Nitrogen)
Kidde IGS using IG-100 are fixed fire extinguishing systems that use the inert gas Nitrogen,
UN number 1066. The purity of the Nitrogen shall be as follows:
•
Nitrogen greater than or equal to 99.7%.
•
Oxygen less than or equal to 10 ppm.
•
Water less than or equal to 10 ppm.
Note:
Only principal contaminants are shown. Other measurements may include: Carbon
Monoxide, Carbon Dioxide, Nitrogen Oxide, and Nitrogen Dioxide most < 20 ppm.
Figure 1-1. IG-100 Pressure/Temperature Curve Isometric Diagram for 200 bar, U.S. Customary Units
Figure 1-2. IG-100 Pressure/Temperature Curve Isometric Diagram for 200 bar, SI Units