option is useful in the heating systems where the solid fuel fired boiler is included in

order to decrease the costs of heating. After the fuel demand alarm has been

cancelled with the STOP button, the additional boiler is turned off again and the work

of the regulator is resumed.

mode [Ar 1]

indicates that the additional output will be working as an alarm output to

which a signalling device can be connected. Boiler sensor failure, error of

overheating or fuel demand will cause the indicator to turn on.

mode [Ar 2] –

the additional output controls the mixing valve. To control the mixing

valve, the household thermostat should be applied to the system. Closing contacts

of the thermostat will make the valve open, and opened contacts will cause the valve

to close. Additionally, the valve is opened to prevent the boiler when the error of

overheating or sensor failure occurs.

mode [Ar 3] –

the additional output controls the boiler emergency chilling system

(e.g. a pump). In the mode, the additional output is turned on when the alarm of

boiler overheating or boiler sensor failure occurs.

mode [Ar 4]

– the additional output controls the devices working simultaneously with

the blower.

CAUTION!

The additional devices should be connected to the UM-1 unit.

Schematics of connections are shown in picture 3.

5.8. Testing the outputs.

To make checking the work of regulator easier it is possible to test the output

systems controlling the blower, pump and the additional boiler turn-on system. The

option is available in the service mode only when the regulating has been stopped,

i.e. the regulator had been in the STOP mode before it entered the service mode.

Selecting [outP] on the display allows with the OK button to turn on the central

heating pump temporarily, selecting [outΠ] will start the blower and choosing [outr]

will cause the additional multifunctional output to be turned on. To test the domestic

hot water pump output select [outu].

5.9. Producer’s settings.

The regulator enables the user to restore the standard settings introduced by the

producer. Select [Prod] on the display and press the OK button to confirm it. When

the option has been activated, the regulator enters the values of particular

parameters given in table 2.

5.10. Exiting the service mode.

To exit the parameters setting mode select [End] on the display and press the OK

button. Also, if no buttons will be pressed for 1 minute, exiting the mode occurs.

Summary of Contents for RK-2001TW4

Page 1: ...OPERATING MANUAL RK 2001TW4 SOLID FUEL FIRED BOILER CONTROLLER Version C112...

Page 2: ......

Page 3: ...erly plugged in the appropriate slots at the back of the device The temperature sensor should be installed in a measurement opening of the boiler The schematics of connecting the regulator and additio...

Page 4: ...maintaining the heating while in the WORK mode 4 Setting the user s parameters When you press the OK button the regulator enters the viewing and setting the user s parameters mode which is signalized...

Page 5: ...de A caption for instance 70 d will be displayed Once the temperature of 75 C in the domestic hot water tank is obtained the regulator returns to its previous status CAUTION To prevent the users from...

Page 6: ...ion of central heating pump check 1 99 F 1min 2 u 50 Domestic hot water programmed temperature 30 60 1 C 50 uh 5 Hysteresis of domestic hot water heating 1 9 1 C 5 ur 0 Domestic hot water pump working...

Page 7: ...tional speed automatically while the temperature of the boiler water approaches the programmed one If the parameter is set to then the gradual regulation of rotational speed is not available and the b...

Page 8: ...at In such case the parameter should be set to the F value 5 3 Preparing the domestic hot water Temperature of the domestic hot water u 50 is the value of temperature which will be maintained in the d...

Page 9: ...89 C then the blower and the pump will be turned on to restore the regular work Applying the STB system allows the user to control the boiler work thoroughly and minimize the risk of overheating 5 6 F...

Page 10: ...ional output controls the devices working simultaneously with the blower CAUTION The additional devices should be connected to the UM 1 unit Schematics of connections are shown in picture 3 5 8 Testin...

Page 11: ...e will be shown on the display In an emergency you should turn off the regulator connect the central heating circulation pump to the power supply permanently ensure the proper firing the fuel in the b...

Page 12: ...rature measurement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Boiler programmed overheating protection 90 99 C 1 C Boiler equipment overheating protection 95 C 1 C Pump turn on...

Page 13: ...13 Picture 3 Schematics of connecting the UM 1 unit...

Page 14: ...14...

Page 15: ...000 4 11 2005 U PN EN 60730 1 2002 A1 2006 U A12 2004 A13 2005 PN EN 60730 1 2005 A14 2006 PN EN 60730 2 9 2006 PN EN 61000 3 2 2006 U PN EN 61000 3 3 1997 A1 2005 A2 2006 IS1 2006 Information on disp...

Page 16: ...Producent P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: