Kewtech KT1780 Instruction Manual Download Page 13

 

   

 

  

UK specific slender probe tips to GS38  

 

and with no need to swap ends

  

Designed to the new internatonal safety  

 

standards IEC 61243-3 / IEC 61010-1  

 

Measurement Category CAT 1V 600V

  

Clear oversize LED indication 

  

AC and DC voltage tests up to 690V

  

Continuity test

  

Clear audible tone

  

Single pole phase test

  

Polarity indication

  

Phase rotation test

  

Self diagonostic test

  

Double moulding gives comfortable grip

  

Auto power on/off

  

Extra bright white light pen torch

  

Probe cover protects user and probe tips

  

IP65

KT1780

2 POLE VOLTAGE DETECTOR

  

Built in test leads

  

Batteries

  

Printed Instruction Manual with  

 

 

Certificate of Conformity

PRODUCT DATA SHEET

ACCESSORIES

OPTIONAL

  

Calibration Certificate

  

Kewprove3 - Proving Unit

  

Kewlok - Locking Off Device

VOLTAGE TEST

SINGLE POLE PHASE TEST

Voltage Range 100~690V AC (45~100Hz)

GENERAL

t. 01494 792 212 

       

kewtechcorp.com

              e:[email protected]

KT1780

SPECIFICATIONS

Voltage Detector

PHASE ROTATION TEST

System

Three-phase 4-wire system
200~690V phase-to-phase
(100~400V earth-to-phase)
AC 50/60Hz

CONTINUITY TEST

Detection Range

0~400K Ω + 50% (23 ± 5ºC)

Test Current

Approx. 1.5µA (battery 3V, 0 Ω)

Internal Battery Consumption

Approx. 80mA (battery 3V, 0 Ω)

Operating ref. conditions -15~55ºC no Condensation max 85% RH

Storage ref. condition

-20~70ºC no Condensation, max 85% RH

Safety standards

IEC 61010-1:2010, IEC 61243-3:2010, IEC 601010-031:2008 
Category: CAT III 690, CAT IV 600V polution deg  2
IEC 61557-7:2007

IP Rating 

IP65 (IEC60529)

Dimensions

243 x 64 x 26 mm

Weight

190g (including batteries)

Batteries

3V (2 x 1.5V AAA / LR03)

Voltage Range

12 - 690V AC/DC

Peak Current

Is <3.5mA (at 690V)

Internal Battery Consumption

Approx. 80mA (battery 3V, measuring 690V AC)

Battery Life

Approx. 1000 operations (30s ON/240s OFF duty)

Nominal Voltage

12/24/50/120/230/400/690V, AC (16~400Hz), DC (±)

Tolerance

(Threshold voltage)

Light on at more than : 7 ± 3V (12V LED), 
: 18 ± 3V (24V LED), : 37.5 ± 4V (50V)
75%±5% of nominal voltage, (120/230/400/690V LED)

Response Time

<0.6s at 100% of each nominal voltage

Reviews: