11
2.3 External Connections
Input 1 --- volt free relay input
–
( close contact to activate the input )
This input is configured as :-
NIGHT SETBACK
Output R1 --- volt free relay output - ( contact closes on activation )
This input is configured as :-
LOW AIR ALARM
Visor Open Input --- a. Connection point for Visor micro switch. ( Switch contact to
close and remain closed in Visor Open condition )
b. Connection point for Visor proximity switch. ( Switch contact to
close and remain closed in Visor Open condition )
Note:- Use input a. OR input b. for the Visor alarm
Power supply --- low voltage DC power supply 15V DC