5.2
FAULT FINDING FLOW CHART
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
Installation & Servicing Instructions
Page : 26
yes
no
yes
Continued on sheet 2
no
Is amber switch light on?
Is there 230V between
terminals SL & N?
Is the boiler switched on?
Faulty Switch Neon
-Replace.
Switch On Boiler.
Check External Controls.
Apply Power To Boiler.
Is the boiler thermostat closed?
Is there 230V between control
box pins 10 & 2 and between
pins 10 and 1?
Is the air pressure switch stuck
in the NO position?
Is there 230V between control
box pins 6 & neutral?
Is there continuity between live
supply from relay to blower &
Neutral through motor
resistance?
Is the f an running?
Is motor overload tripped?
Is there wiring continuity
& in-line connector
to motor?
Boiler return is too hot. Allow
to cool. OR faulty thermostat -
Replce.
Check continuity (see section
5.3)
Faulty pipe connections to Air
Press. Switch. OR Faulty Air
Press. Switch - Replace.
Control box faulty.
Motor/Fan fault y - Replace.
Wait for motor to cool.
Identify & correct break.
START
no
no
yes
no
yes
yes
no
no
yes
no
yes
yes
no
no
yes
no
yes
Is the motor relay operating?
yes
Relay not secure in socket or
relay faulty - replace
no