B-14
BOP-1K 091719
B.38
[SOURce:]CURRent[:LEVel]:PROTect[:BOTH] QUERY
CURR:PROT[:BOTH]?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT[:BOTH]?
Long Form: [SOURce:]CURRent[:LEVel]:PROTect[:BOTH]?
Returns <value>, <value>
Description: Identifies the protection limits for current (source, sink), the maximum current the unit will source.or
sink
B.39
[SOURce:]CURRent[:LEVel]:PROTect:MODE COMMAND
CURR:PROT:MODE
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:MODE (EXT | FIX | LESS |)
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:MODE (EXTernal | FIXed | LESSer |)
Description: Determines how current protection limits are controlled in voltage or current mode of operation.
FIXED - Allows the limits to be controlled by digital signals from either the keypad (if the unit is in local
mode) or SCPI command (if the unit is in remote mode).
EXTERNAL: Allows both current and voltage limits to be controlled by analog signals applied to the
analog port; limits set from the keypad or SCPI command have no effect (see PAR. 3.4.5).
LESSER LIMIT: Allows protect limit to be automatically selected from either 1) the external analog limit
CURRent applied to the Analog I/O port or 2) the value set from the keypad or SCPI command).
Whichever limit has a lower absolute value (closest to zero) has effect.
B.40
[SOURce:]CURRent[:LEVel]:PROTect:MODE? QUERY
CURR:PROT:MODE?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:MODE?
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:MODE?
Returns FIXED, EXTERNAL or LESS
Description: Identifies how current protection limits are controlled. (See PAR. B.39 for details).
B.41
[SOURce:]CURRent[:LEVel]:PROTect:NEGative COMMAND
CURR:PROT:NEG
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:NEG <value>
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:NEGative <value>
where <value> is between minimum (box) value (Figure 1-3) and 1% above rated (nominal) output
current.
Description: Establishes the negative protection limit for current, maximum is 1% greater than rated (nominal) out-
put current.
B.42
[SOURce:]CURRent[:LEVel]:PROTect:NEGative? QUERY
CURR:PROT:NEG?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:NEG?
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:NEGative?
Returns <value>
Description: Identifies the negative protection limit for current.
B.43
[SOURce:]CURRent[:LEVel]:PROTect:POSitive COMMAND
CURR:PROT:POS
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:POS <value>
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:POSitive <value>
where <value> is between minimum (box) value (Figure 1-3) and 1% above rated (nominal) output
current.
Description: Establishes the positive protection limit for current, maximum is 1% greater than rated output current.
B.44
[SOURce:]CURRent[:LEVel]:PROTect:POSitive?
QUERY
CURR:PROT:POS?
Syntax:
Short Form: [SOUR:]CURR[:LEV]:PROT:POS?
Long Form: [SOURce:]CURRent[:LEVel]:PROTect:POSitive?
Returns <value>
Description: Identifies the positive protection limit for current.
Summary of Contents for BOP-ME 1KW
Page 2: ......
Page 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Page 42: ......
Page 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Page 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Page 76: ......
Page 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...