DYNAMICS: The dynamic response of the BOP output are tabulated in Table 1-3 in both the
time domain (Output response to a step program) and in the frequency domain (bandwidth)
for large and small signals.
1.5
MISCELLANEOUS FEATURES
A)
OUTPUT RANGE: The BOP can be locally (front panel) adjusted, or remotely programmed,
from (-) 100% to (+)100% of its specified d-c voltage and current range. The Class A bipolar
output stage permits operation as either a SOURCE OR A SINK. (See FIG. 1-2.)
NOTE:
Operation in the second quadrant of the graph must be derated as indicated.
TABLE 1-3. DYNAMIC SPECIFICATIONS
DYNAMIC SPECIFICATIONS
VOLTAGE CHANNEL
CURRENT CHANNEL
BOP 500M
BOP 1000M
BOP 500M
BOP 1000M
Closed Loop Gain
50 V/V
100 V/V
8 mA/V
4 mA/V
Bandwidth [d-c to f-3 dB]
5.3 KHz
1.8 KHz
2.0 KHz
1.5 KHz
Programming Time Constant
30
µ
sec.
88
µ
sec.
80
µ
sec
106
µ
sec.
Large Signal Frequency Response
6 KHz
1.9 KHz
2.5 KHz
1.6 KHz
Slewing Rate
18V/
µ
sec.
12V/
µ
sec.
1.25 mA/
µ
sec
0.4 mA/
µ
sec.
Load Recovery Time Constant
25
µ
sec.
75
µ
sec.
25
µ
sec.
50
µ
sec.
FIGURE 1-2. BOP OUTPUT CHARACTERISTIC