USER MANUAL
If the cable has not armature, and it is easy-to-reach, the area of
conductor break may be found with mini-sensor of the MD-01 model.
The mini-sensor MD-01 is shown in Figure 19. Connect the mini-
sensor to the SONDE jack.
Figure 19
– Mini-sensor MD-01
The sensor is compact, and it provides more accurate tracing in case
of close location of wires.
When you use the MD-01 sensor, switch the Transmitter to the mode
of limitation of the input voltage to the level of 30V.
WARNING!
Do not supply the voltage of more than 42V to the current-
collecting nozzle of the mini-sensor probe
If the cable is easy-to-reach and unshielded, the area of conductor
break may be found with the MD-01 mini-sensor. Set the switch of
the mini-sensor int
o the “O” position. The mini- sensor registers an
electric field near the conductors.
In Figure 20 shows the conductor break locating diagram.
Figure 20
– Connection diagram and signal strength for
conductor break locating on the unshielded lines
Wire break area
Connect
Ground