14.18. Data sheet leakage sensor (KLS03, KLS03-ROPE10/20)
Connectivity
AlarmManager-BASIC (KAM-BASIC)
AlarmManager-PRO (KAM-PRO)
MultiSensor-RF (KMS-RF) (with KIO1 Power-Adapter)
MultiSensor-LAN (KMS-LAN)
MultiSensor-LAN-RF (KMS-LAN-RF)
Chassis sensor
Ni/Au, sensitivity 1ml water
Rope sensor
Conductive polymeric cable, sensitivity: 10ml water on
20cm length
LED
ALARM LEAKAGE (Red)
STATE OK (Green)
Connectors
2 x RJ45 for standard patch cables
Power supply
Via Kentix system jack (RJ45)
Daisy chaining - linking
Up to 5 sensors, max. 50m combined cable length
Chassis
Material: PS 80 x 80 x 80 mm
Weight: ca. 200g (KLS03), 0,75kg (KLS03-ROPE-10), 1kg
(KLS03-ROPE-20)
Color: RAL7035
Protection class: IP65
Cable glant
M20
Environment
Temperature -25°C - 70°C
Humidity 5-85%, non condensing
Types
KLS03, KLS03-ROPE-10, KLS03-ROPE-20
Protection class
IP65
Content of delivery
10m patch cabel
Additional fitting for chaining
(Cable glant M20)
Approvals
CE
Page
(07-2018, subject to change)
kentix.com
125