Man-1078_Sigma_CP_22
Page 18 of 24
61
CONFIGURE Z1 FOR I.S BARRIER
Detection threshold changed for use with IS barrier
62
CONFIGURE Z2 FOR I.S BARRIER
63
CONFIGURE Z3 FOR I.S BARRIER
64
CONFIGURE Z4 FOR I.S BARRIER
65
CONFIGURE Z5 FOR I.S BARRIER
66
CONFIGURE Z6 FOR I.S BARRIER
67
CONFIGURE Z7 FOR I.S BARRIER
68
CONFIGURE Z8 FOR I.S BARRIER
CODE
FUNCTION
COMMENTS
71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the
zone so that the control panel can be
used on older systems that had no short
circuit monitoring.
72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
74*
ZONE 4 SHORT CIRCUIT INDICATES ALARM
75*
ZONE 5 SHORT CIRCUIT INDICATES ALARM
76*
ZONE 6 SHORT CIRCUIT INDICATES ALARM
77*
ZONE 7 SHORT CIRCUIT INDICATES ALARM
78*
ZONE 8 SHORT CIRCUIT INDICATES ALARM
81*
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset itself when
sounders are operating
82*
ZONE 2 NON-LATCHING
83*
ZONE 3 NON-LATCHING
84*
ZONE 4 NON-LATCHING
85*
ZONE 5 NON-LATCHING
86*
ZONE 6 NON-LATCHING
87*
ZONE 7 NON-LATCHING
88*
ZONE 8 NON-LATCHING
91
ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs.
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
A1*
ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously
before an alarm is generated.
A2*
ZONE 2 ANY ALARM DELAYED
A3*
ZONE 3 ANY ALARM DELAYED
A4*
ZONE 4 ANY ALARM DELAYED
A5*
ZONE 5 ANY ALARM DELAYED
A6*
ZONE 6 ANY ALARM DELAYED
A7*
ZONE 7 ANY ALARM DELAYED
A8*
ZONE 8 ANY ALARM DELAYED
C1
ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders.
On 2 wire “T” series panels this enables individual zones to be
configured for use with conventional (non 2-wire) detector
bases.
SOFTWARE VERSIONS SIGMA242.HEX and above only
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4
ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8 SOUNDERS INHIBITED
E1*
ZONE 1 WILL NOT OPERTATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching
function to prevent ring around on interconnected panels.
SOFTWARE VERSIONS SIGMA242.HEX and above only
E2*
ZONE 2 WILL NOT OPERTATE FIRE RELAY
E3*
ZONE 3 WILL NOT OPERTATE FIRE RELAY
E4*
ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5*
ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6*
ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7*
ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8*
ZONE 8 WILL NOT OPERTATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with EN54-2