9. Safety control
Functions
Minutes delay for the compressor start-up:
At the beginning of energizing, 3-minutes delay should be taken to start the compressor. While
after the stop of the compressor, 7-minutes delay should be taken to restart the compressor.
Compressor discharge temperature protection:
When the temperature of compressor discharge is higher than 125°C (257°F), the compressor
will stop. Once the temperature is lower than 90°C (194°F), the compressor can be started
again.
Reverse phase protection relay:
The reverse phase protection relay will make the unit not start, when the power supply source is
in correctly conneted.
The checking of phase order is just carried out at the first time of electrifying. If malfunction
happens then the checking will be going on until the order of phase is right, and the error code
will be displayed on the board. If there is no problem in the first checking, then it will be omitted.
High pressure and low pressure protection :
When high pressure is equal or higher than 638 Psi, and lower pressure is equal or lower than
21Psi, the unit will stop.
Summary of Contents for KRFN1050CFAN3
Page 27: ...Rooftop KRFN Kentatsu Performance 27 3 Dimensions drawings KRFN220CFAN3 KRFN260CFAN3 Unit mm...
Page 28: ...Kentatsu Rooftop KRFN 28 Performance...
Page 29: ...Rooftop KRFN Kentatsu Performance 29...
Page 30: ...Kentatsu Rooftop KRFN 30 Performance KRFN300CFAN3 KRFN350CFAN3 Unit mm...
Page 31: ...Rooftop KRFN Kentatsu Performance 31...
Page 32: ...Kentatsu Rooftop KRFN 32 Performance KRFN440CFAN3 KRFN530CFAN3 Unit mm...
Page 33: ...Rooftop KRFN Kentatsu Performance 33...
Page 34: ...Kentatsu Rooftop KRFN 34 Performance KRFN600CFAN3 KRFN700CFAN3 Unit mm...
Page 35: ...Rooftop KRFN Kentatsu Performance 35...
Page 36: ...Kentatsu Rooftop KRFN 36 Performance KRFN880CFAN3 KRFN1050CFAN3 Unit mm...
Page 37: ...Rooftop KRFN Kentatsu Performance 37...
Page 38: ...Kentatsu Rooftop KRFN 38 Performance 4 Wiring diagrams KRFN220CFAN3 KRFN260CFAN3...
Page 39: ...Rooftop KRFN Kentatsu Performance 39 KRFN300CFAN3...
Page 40: ...Kentatsu Rooftop KRFN 40 Performance KRFN350CFAN3...
Page 41: ...Rooftop KRFN Kentatsu Performance 41 KRFN440CFAN3...
Page 42: ...Kentatsu Rooftop KRFN 42 Performance KRFN530CFAN3...
Page 43: ...Rooftop KRFN Kentatsu Performance 43 KRFN600CFAN3...
Page 44: ...Kentatsu Rooftop KRFN 44 Performance KRFN700CFAN3...
Page 45: ...Rooftop KRFN Kentatsu Performance 45 KRFN880CFAN3 KRFN1050CFAN3...
Page 118: ...Kentatsu Rooftop KRFN 118 Installation Low pressure protection Eeprom error...
Page 121: ...Rooftop KRFN Kentatsu Installation 121 Protection of outdoor ambient temperature...