INBUILT FLUE INSTALLATION
Cut a 260mm (minimum) square penetration for the passage of the flue pipe and casing
through the ceiling. If preferred there can be no ceiling in the framed enclosure. Cut an
opening through the roof to position the outer casing through the roof and support if
necessary with bracing angle to suitable anchorage points.
Join the required number of 150mm flue pipes by inserting the swaged ends of the upper
piece into the plain end of the lower piece. Drill and fix each length with three stainless
rivets or self-tapping screws. It is important that each 150mm flue pipe joint is sealed with
commercially available flue sealing compound, including the joint between the flue
spigot and the first length of flue pipe.
Ensure a suitable flashing is installed on any roof penetration point. Flash the outer casing
to the roof, to make a permanent, weatherproof seal.
Minimum Installation Clearances (mm)
Model
Model No.
A
B
C*
D
E
F
G
H
I
Rata
KWF295-6938
25
500
300
200
840
59
2000
1200
160
Logfire II
KWF295-6937
25
500
300
200
840
59
2000
1200
160
Logfire inbuilt
(non clean-air)
KWF296-6915
25
500
300
200
800
59
2000
1200
160
*
Floor protector from front of fascia.
TABLE 2
Inbuilt Installation
Insert installation
FIG. 1
Plan Elevation
Side Elevation
Masonry Cavity
Timber Cavity
4
Open the door of the fire and manoeuvre the fascia over the open door taking care not
to scratch the paint on the door. Align holes in fascia with screw locater holes in outer
cabinet.
Close the fire door and secure fascia to fire outer cabinet with screws and washers
supplied. Check that door is central in fascia opening and tighten screws once fascia is
in the desired position.
Refit louvers by placing in position at a 45° angle into the louver opening. Place the first
louver bar at the top behind the front of the fascia. Rotate louver into position and pull
down to locate bottom pins in position.
Summary of Contents for KWF295-6937
Page 2: ......