Kendrion Kuhnke Automation GmbH
System Description
17
17 May 2021
Installation
Kuhnke FIO I/Os mount on 35 mm x 7.5 mm rails to DIN EN 50022.
Position
Mount with rail horizontally with the modules' multiple socket connectors pointing away from the wall.
To ensure that enough air gets in through the ventilation slots, leave at least 20 mm to the top and 35
mm to adjacent devices or cabinet surfaces. Leave at least 20 mm of lateral distance to third-party
units and cabinet surfaces.
Order of Modules in Multi-FIO Systems
NOTE
In order to ensure that the entire FIO system works properly, arrange the FIO modules by their
specific E-bus load, placing the modules with the highest E-bus load immediately next to the
head module (bus coupler or controller). Take account of the head module's maximum bus
load.
If possible, place the Kuhnke FIO Safety I/O modules immediately next to the head module.