INSTALLATION INSTRUCTIONS

MRIPSF-480_F-7499_031919

Wiring Procedure – Multiple Power Supply/DC Filters

Installations involving many luminaires within a single shielded room may require multiple power supplies (and 
EMI filters) to handle the load. Please see “Maximum Fixture Connection” to determine if the application requires 
multiple supplies. Wiring guidelines are the same as the previous section, please see Figure 4 below.

Wiring Procedure – Dimming Line

All Kenall MRI luminaires can dim via 0-10V control. Kenall recommends the Lutron Diva (DVSTV) and Lutron Nova 
T (NTSTV-DV) series to ensure the full range of dimming can be achieved. 

NOTE:

 In the situation where the luminaire groups are controlled by separate dimming circuits, it is imperative that 

each circuit utilizes a dedicated control line filter (Kenall MRIFD-1A or equivalent). 
1.  Run low-voltage wiring, 18-GA minimum, from the dimmer to the control line filter through the grounded 

conduit installed in “0-10V Dimming Filter Mounting Procedure”.

WARNING: To prevent electrical shock, manually discharge the internal filter capacitors by 

temporarily connecting field terminals to ground (wearing insulated gloves is recommended).

2.  Solder the dimming line positive (violet) and negative (gray) conductor to solder terminal lugs L1 and L2, 

respectively.

3.  Remove lose hardware supplied on the ground screw terminal marked with the Green label and install a 

ground wire identical in size and insulation rating to the grounded and ungrounded circuit supplied conductor, 
except it shall be colored Green or Green-Yellow. Use a crimped or solder-type ring connector (not supplied, see 
Figure 5).

Figure 4: Multiple-Supply System Schematic

Fixture 

Group 1

Fixture 

Group 2

Fixture 

Group N

RED

RED

BLACK

BLACK

BLACK

RED

COMMON

HOT

120-277VAC

50/60 Hz

MRIPSF-480

AC

IN

AC

IN

AC

IN

+

24V

+

24V

+

24V

EMI

Filter

EMI

Filter

EMI

Filter

EMI

Filter

+

0-10V Dimmer

(by others)

MRIFD-1A

(or equal)