Rooftop installation

Rooftop installation

If the outdoor unit is installed on a roof structure, be sure to level 
the unit.

Ensure the roof structure and anchoring method are adequate for 
the unit location.

If the outdoor unit is installed on roof structures or external walls, 
this may result in excessive noise and vibration, and may also be 
classed as non-serviceable installation.

Pipe Length Elevation and Additional Quantity of Gas

Model Number Discharge Pipe  

Diameter

Suction Pipe 

Diameter

Standard 

Length (m)

Maximum 

Length (m)

Maximum  

Height (m)

Additional 

Refrigerant (g/m)

KSV25HRF

Ø6.35 mm (1/4”)

Ø9.52 mm (3/8”)

7.5

15

10

16

KSV35HRF

Ø6.35 mm (1/4”) 

Ø9.52 mm (3/8”)

7.5

20 

10 

16

KSV52HRF

Ø6.35 mm (1/4”) 

Ø12.70 mm (1/2”) 

7.5

25 

10 

16

KSV70HRF

Ø6.35 mm (1/4”) 

Ø15.88mm (5/8”) 

7.5 

25 

10 

40

KSV80HRF

Ø6.35 mm (1/4”) 

Ø15.88mm (5/8”) 

7.5

30 

10 

40

KSV25CRF

Ø6.35 mm (1/4”) 

Ø9.52 mm (3/8”)

7.5

15 

10 

12

KSV35CRF

Ø6.35 mm (1/4”) 

Ø9.52 mm (3/8”) 

7.5

20 

10 

12

KSV70CRF

Ø6.35 mm (1/4”) 

Ø15.88 mm (5/8”) 

7.5

25 

10 

12

WARNING

caution

• 

 The outdoor unit is charged with the refrigerant for standard 

pipe length of 7.5m. 

• 

 When the connecting pipe length is longer than the standard 

length, additional refrigerant should be added into the unit 

according to the above table through the service port on 3-way 

service valve on the outdoor unit.

• 

 PLEASE MAINTAIN THE SHORTEST DISTANCE (3 TO 5 

METRES) AND SHORTEST MISALIGNMENT POSSIBLE 

BETWEEN THE INDOOR AND OUTDOOR UNITS.

• 

 The maximum allowance length and height is based  

on reliability. Exceeding the maximum may cause poor 

performance or malfunction. 

• 

 When the level difference between indoor and outdoor units 

is greater than the maximum height of 10 metres, or when 

the outdoor unit is installed above the indoor unit, an oil trap 

should be installed every 5-7 metres.

maximum length

maximum length

oil trap

maximum height

maximum height

piping length under 7.5m

piping length 7.5m or more

A

A

B

B

indoor unit

indoor unit

outdoor unit

outdoor unit

Summary of Contents for KSV25CRF

Page 1: ...Inverter Air Conditioner Installation Manual KSV25CRF KSV35CRF KSV70CRF KSV25HRF KSV35HRF KSV52HRF KSV70HRF KSV80HRF Refrigerant R32 ...

Page 2: ...itioner but contact your local Electrolux Customer Care Centre Meanings of symbols used in this manual are shown below WARNING warning This symbol indicates information concerning your personal safety WARNING caution This symbol indicates information on how to avoid damaging the appliance TIPS INFORMATION important This symbol indicates tips and information about use of the appliance ENVIRONMENTAL...

Page 3: ...at they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnected Please read this installation manual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install and test the air conditioner properly Electrical work must be installed by ...

Page 4: ...tric drill Hole core drill 55mm 70mm Flaring tool specifically designed for R32 or R410a refrigerant Specified torque wrenches Spanner half union A glass of water Hexagonal wrench 6mm Gas leak detector 2 stage vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Number Description Quantity 1 Indoor unit mounting plate 1 2 Clip anchor not supplied 3 Self tapping...

Page 5: ...ce to obstruction air inlet side space to the wall space to the wall space to the ceiling space to the floor air outlet side 15cm or more 200cm or more 15cm or more 2 5 0 c m o r m o re 15cm or more space to the wall air outlet side 30cm or more 50cm or more space to the wall 50cmormore 20cm orm ore 150cm orm ore 1 8 9 10 11 12 13 14 15 16 17 7 6 5 4 ...

Page 6: ... and efficient operation of the unit Avoid the following sites where strong heat sources vapour flammable gas or volatile liquids are emitted high frequency electro magnetic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot...

Page 7: ...2 KSV35CRF Ø6 35 mm 1 4 Ø9 52 mm 3 8 7 5 20 10 12 KSV70CRF Ø6 35 mm 1 4 Ø15 88 mm 5 8 7 5 25 10 12 WARNING caution The outdoor unit is charged with the refrigerant for standard pipe length of 7 5m When the connecting pipe length is longer than the standard length additional refrigerant should be added into the unit according to the above table through the service port on 3 way service valve on the...

Page 8: ... not supplied Securing the outdoor unit Anchor the outdoor unit by fixing the 4 holes existent in its base with 4 bolts and nuts of φ10 mm tightly not included Place the outdoor unit over a horizontal concrete or rigid surface never directly over grass or earth A B air inlet air inlet air outlet Model Outdoor unit dimensions W x D x H mm Dimension A mm Dimension B mm KSV25HRF CRF 776 x 320 x 540 5...

Page 9: ...the indoor unit has two way drainage design During installation the indoor unit should slightly slant to water tray s outlet for smooth drainage of condensate water Mounting plate type A 55mm 55mm 143 135 80 542 235 Mounting plate type B 55 55 31 87 1000 219 694 98 78 256 78 Fit the mounting plate and drill holes in the wall according to the wall structure and corresponding mounting points on the ...

Page 10: ...10 Indoor unit installation Indoor unit installation Mounting plate type C indoor unit 253 179 746 326 65 65 50 163 90 6 74 105 ...

Page 11: ...lways use a wall hole conduit when drilling metal grids metal plates or the like 5 For models with a cooling capacity greater than 4500W remove and dispose the two polystyrene lateral rear supports from the indoor unit before the installation remove both supports Installation of drain hose 1 Connect the drain hose to the outlet pipe of the indoor unit Bind the joint with vinyl tape outlet pipe of ...

Page 12: ...he wiring only Cut off the tailings 1 and tailings 2 when routing both the wiring and piping indoor unit outline connection piping 43 2 The drain hose can be connected at two different positions Use the most convenient position and if necessary exchange the position of drain cap and drain hose The drain hose is connected at the rear left side of the indoor unit when you receive the product drain h...

Page 13: ...from the right side piping on the right side drain hose from the left side piping on the right side drain hose from the right side piping on the left rear side drain hose from the left side piping on the left side drain hose from the left side WARNING caution When refrigerant pipes and the drain pipe are fitted to the same side ensure that the bulk does not push the unit away from the wall when in...

Page 14: ...of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never cross connect or interwind the power wire with any other wiring Do not allow the piping to be exposed out from the back of the indoor unit If part of the drain hose is positioned inside the room wrap it with insulating materials so as to prevent condensed water from dropping 5 Hang the mounting slots of ...

Page 15: ...ipe tube Face the end of the copper pipe tube in a downward direction as you remove burrs in order to avoid burrs dropping into the tubing pipe reamer face down c Put the flare nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal flare nut copper tube WARNING caution It is not possible to put them on after flaring work d Flaring work...

Page 16: ... conditions b Wrap the insulation material around the connecting portion Cover the indoor unit pipe and the connection pipe with the heat insulation material Bind them together with vinyl tape so that there is no gap insulating material Isolate the suction pipe from the liquid pipe heat insulation suction line pipe liquid line pipe Wrap the insulated pipes with vinyl tape in the rear section for p...

Page 17: ...e for KSV52HRF suction pipe discharge pipe for KSV52HRF Make sure to follow the torque table value as below Outer diameter mm Torque N m 6 35 1 4 15 20 9 52 3 8 35 40 12 70 1 2 50 55 15 88 5 8 60 65 19 05 3 4 70 75 Piping formation a Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with narrow vinyl tape and wide vinyl tape If you want to...

Page 18: ...A circuit breaker with proper capacity must be installed according to AS3000 and applicable local electrical safety regulations 5 In case of problems in power supply the air conditioner must not be installed before the customer fixes the problem 6 Be sure the power supply matches the air conditioner 7 Ensure the live wire neutral wire and earth wire in the power socket are properly connected 8 Ina...

Page 19: ...th insulating tape so that they do not touch any electrical or metal parts 5 Secure the wires firmly with the cable clamp 6 Put the wiring cover back and screw it 7 Reinstall the front panel Installation WARNING warning All wires between indoor and outdoor units must be connected by a qualified electric contractor If the length of the power cord is not enough please contact your installer for new ...

Page 20: ...ARNING caution After confirming the above conditions prepare the wiring as follows The screws which fasten the wiring to the terminal block may come loose from vibrations during transportation Check and make sure all screws are well fixed Otherwise it could cause burn out of the wires Be sure the circuit capacity is sufficient Ensure the starting voltage is maintained at over 90 of the rated volta...

Page 21: ...g efficiency drops Moisture in the refrigeration circuit may freeze and block the capillary tubing Water may lead to corrosion of parts in the refrigeration system Therefore the indoor unit and tubing between the indoor and outdoor units must be tested for leakage and evacuated to remove any non condensables and moisture from the system Air purging with a vacuum pump Preparation Check that each tu...

Page 22: ...pump for vacuumisation At the beginning slightly loosen the flare nut of the low pressure valve to check if there is air coming inside if operation noise of the vacuum pump has been changed the reading of multimeter is 0 instead of minus Then tighten the flare nut 5 Keep vacuuming for more than 15 minutes and make sure the reading of multimeter is 1 0 x 10 Pa 76cmHg Then fully close the low handle...

Page 23: ...fore installation is finished completely Electric wiring must be connected correctly and securely Stop valves of the connection pipes should be fully opened All the impurities such as scraps and waste must be cleared from the unit Operation test method Switch on power and press ON OFF button on the remote controller to start the operation Press MODE button to select the COOL HEAT if applicable FAN...

Page 24: ...s the unit securely mounted Is the unit readily accessible without special equipment Has the appropriate size circuit and fuse circuit breaker been fitted Has the unit been tested and confirmed to operate correctly Has the user of the air conditioner been shown how to use the air conditioner CUSTOMER PLEASE RETAIN WITH YOUR PURCHASE DOCUMENTS IN A SAFE PLACE Model Number___________________________...

Page 25: ...ge in accordance with the rated voltage marked on the nameplate It may cause electric malfunction or damage the unit Is the electric wiring or piping connection installed correctly and securely It may cause electric malfunction or damage the parts Has the unit been securely earthed It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damage the parts Is ...

Page 26: ...26 Notes Notes ...

Page 27: ...ct claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi incorrect improper...

Page 28: ...inator com au NEW ZEALAND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call into your retailer phone or email our customer care team or visit our website Kelvinator We are part of the Electrolux family Share more of our thinking at electrolux com au ...

Reviews: