Kelvin RH015 Installation, Operation And Maintenance Manual Download Page 7

 

 

 
 

MAINTENANCE

 

 

 

The RH Models are relatively maintenance free.  Electric motor bearings are 

prelubricated and should be lubricated as shown below. 
 
 

Relubricate Intervals 

 
 

The following intervals are suggested as a guide. 

 

 

Hours of Service Per Year

 

 

Suggested Relube Interval

 

 

5000 

 

Every 5 years 

Continuous 

 
Normal Application 

 

Once a year 

Continuous 

 
In high ambient, or dirty or moist location; or 
where motor is idle for six months or more, 
and applications with high vibration or where 
shaft end is hot (pumps – fans). 

 

Every 6 months 

 

 
 

 

Lubricant

 

 

Use high grade ball bearing grease.  Use consistency of grease suitable for class of 

insulation stamped on nameplate, as follows: 
 

 

Insulation 

Class 

 
 

Consistency 

 
 

Type 

 
 

Typical Grease 

 

B or F 

 

#3 

 

Lithium Base 

 

Shell Cyprina #3 

 

 

 

Procedure

 

 
 

If motor is equipped with Zerk fitting, clean tip of fitting and apply grease gun.  Use one 

to two full strokes on motors. 
 

CAUTION

 

 

Keep grease clean!  Do not mix petroleum grease and silicone grease in motor bearings.

 

 

The cooling coils may become clogged with leaves, paper, incineration ash or other 

airborne dirt.  Normal rainfall will generally clean the coil, but if not, clean with compressed air 
or if oil is involved in the fouling use steam. 
 
 

Summary of Contents for RH015

Page 1: ...1 INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS 5050 South National Dr Knoxville TN 37914 Telephone 317 227 2929 ...

Page 2: ...D HEAT EXCHANGERS TABLE OF CONTENTS TOPIC PAGE Model Nomenclature 2 Inspection 2 Handling and Moving 2 Location 3 Assembly of Unit 3 Electrical Wiring 5 Piping 5 Start Up and Operation 5 Freeze Protection 5 Maintenance 6 Replacement Parts 7 ...

Page 3: ... each unit is made and shipped in modules one module for the RH 035 and RH 045 two modules for the RH 055 RH 070 and RH 085 And as a preventative measure to guard against transportation damage each module is shipped on its side with the legs removed and crated on heavy duty skids It is advisable to move the modules as close as possible to its final location before uncrating It is up to the unit ri...

Page 4: ...4 Fig 1b Lifting an RH module with slings ...

Page 5: ...assembled except for the mounting legs Mounting legs are furnished with the necessary bolts nuts and washers The legs are not adjustable and are most easily assembled to the unit when the unit is still laying on its side as shipped Each leg is fastened to the bottom of the coil plenum by four bolts furnished with the unit Reference Figure 2 The larger RH Models RH055 and up are delivered as two se...

Page 6: ...ctions should be made to the higher of the two openings supplied per module the outlet connection is made with the lower of the openings This piping arrangement is necessary to insure a cross counterflow coolant passage thru the unit for maximum heat transfer In most RH applications a surge tank is recommended to maintain a safe coolant level in the system and allow entrained air to escape from th...

Page 7: ...mps fans Every 6 months Lubricant Use high grade ball bearing grease Use consistency of grease suitable for class of insulation stamped on nameplate as follows Insulation Class Consistency Type Typical Grease B or F 3 Lithium Base Shell Cyprina 3 Procedure If motor is equipped with Zerk fitting clean tip of fitting and apply grease gun Use one to two full strokes on motors CAUTION Keep grease clea...

Page 8: ...8 REPLACEMENT PARTS If it becomes necessary to order parts please mention all identifying numbers such as model number or part number as found on the Kelvion nameplate ...

Reviews: