Programming mode
Programming  mode  (see  the  menu  structure)  allows  the  switching  thresholds  and 

switching functions to be set.

Example: Changing the switching threshold
The switching threshold to be changed is selected with SELECT (see the menu struc-

ture). The currently selected menu item is indicated at the bottom of the display: I, II, 

Low, High, Fct. The arrows point to the corresponding designations. E.g.: if the arrows 

point to I and High --> the high switching threshold of switch output 1 can be changed.

This value is then released for change by pressing ENTER (flashing arrow). The value 

is decreased with SELECT and increased with ENTER. If no button is pressed for about 

5 seconds, the programming device saves the value displayed to the pressure switch 

(the arrows stop flashing). 

Switching functions (Fct.)
Various functions can be configured for the switch outputs.
Hysteresis (H):  

When  the  high  switching  threshold  is  exceeded,  the  output 

closes. It only opens again when the value goes below the low 

switching threshold. Application example: 2-point controller.

Window (F)

The switch output is closed between the low and high swit-

ching  thresholds.  Outside  this  range  it  is  open.  Application 

example: Alarm when the pressure is outside a defined range.

Normally Open (no):   The switch contact is normally open.
Normally Closed (nc):  The switch contact is normally closed (inverse of NO)
Off (OFF)

The switch contact is always open

To  change  the  corresponding 

switching function, press ENTER 

in  the  programming  mode  re-

peatedly  until  the  required 

function  is  displayed.  Press  

SELECT to go to the next menu 

item:  this  simultaneously  saves 

the  displayed  switching  function 

to the pressure switch.

P/bar

P/bar

High

NO

NC

NC

t

t

1

0

1

0

0

1

0

1

Low

High

Low

NO

window function

hysteresis function

        Programmer dV-22 PP                                                           - 9 -

Summary of Contents for PA-22 PS

Page 1: ... May 2011 OPERATING MANUAL PRESSURE SWITCH PA 22 PS PROGRAMMER dV 22 PP PROGRAMMING SOFTWARE Pressure Switch Console ...

Page 2: ...upply connection M12 plug 6 Converter connection connector plug 6 Pressure switch connection M12 socket 6 Display7 Navigating in the Menu Functions of the keys 7 Menu structure 8 Programming mode 9 Switching thresholds 9 Switching functions 9 Software Pressure switch console Selection of the serial port 10 Selection of the pressure unit display 10 Read out and programming of the pressure switch 10...

Page 3: ...y 0 5 seconds If a meter is connected to the analog output it must have an internal resistance of at least 30 kΩ Though the pressure switches are already configured at the factory the configuration can be changed via the dV 22 PP programmer Time delay can only be changed with a PC laptop running Pressure Switch Console software Connection diagram NPN switch output with external load RL PNP switch ...

Page 4: ... 5 2 3 6 4 4 www keller druck com 1 M 12 plug Power supply connection 8 40 V DC 2 5 pole connector Connection to PC laptop with a converter K 107 K 104B 3 M 12 socket Connection of the pressure switch 4 LED Indicates the status of the switches switch 1 and switch 2 5 LCD Main display 6 Keys SELECT and ENTER ...

Page 5: ...ion Programming with a PC Laptop If an interface cable from KELLER K 107 K 104 B is connected to the programmer programming can be carried out with a PC laptop using the Pressure Switch Con sole software In this case the power supply for the programmer comes directly via the converter Power supply The programmer is connected between the power supply and the pressure switch Pressure switch Software...

Page 6: ...ctly with the application and the functions of the pressure switch remain preserved Attention The switch outputs are inactive open during the programming mode Connection to PC Binder Plug The connector plug is used for communication with a PC laptop The interface cable K 107 K 104B can be con nected here Pressure switch connection M12 socket The pressure switch is connected to the M12 socket If ne...

Page 7: ...nd the status of the switch outputs with LED s LEDs for the indication of the status of the switch outputs Pressure measuring units Pressure value Programmer dV 22 PP 7 Menu Navigation Navigation in the display menu is made with the two keys SELECT and ENTER Functions of the keys SELECT Navigate forwards within the menu ENTER Select the menu item ...

Page 8: ...itch output II Low switching threshold Low Switch output I Switching function Fct Hysteresis window NO NC OFF Switch output II Switching function Fct Hysteresis window NO NC OFF Return to Normal Mode END Change the pressure display unit Unit bar SELECT Change the settings of the switch outputs S Set Programming mode Switch output I High switching threshold High Pressure display normal mode Show th...

Page 9: ...g functions Fct Various functions can be configured for the switch outputs Hysteresis H When the high switching threshold is exceeded the output closes It only opens again when the value goes below the low switching threshold Application example 2 point controller Window F The switch output is closed between the low and high swit ching thresholds Outside this range it is open Application example A...

Page 10: ...unit bar PSI or MPa in which the program displays the pressure values can be selected Read out and programming of the pressure switch By pressing Read out the data of the pressure switch which is connected to the programmer is read The configurations switching thresholds switching functions switching time delays can now be changed for the switch outputs 1 and 2 Press Program to load the changed va...

Page 11: ...e pressure switch and the status of the switch outputs can be displayed Press Display to show these values How ever the actual pressure value can only be displayed if the pressure switch has an analog output Pressure Switch Console 11 A pressure trend curve can be dis played and recorded graphically with the KELLER Read30 soft ware ...

Page 12: ...eclaration is valid for products of which a drawing marked with the CE sign exists and which are produced according to this drawing This explanation has no validity without such a drawing As criteria for the electromagnetic compatibility the following norms are applied EN 61000 6 2 EN 61000 6 3 EN 61000 6 4 This declaration is given for the manufacturer KELLER AG für Druckmesstechnik St Gallerstra...

Reviews: