K-O2 Oxygen Sensor 

5/20/2022 

Kele, Inc. • 3300 Brother Blvd. • Memphis, TN  38133 

Page 9 

 

www.kele.com

 

 

5.1  C

ALIBRATION 

G

ASES

 

Pure nitrogen zero gas and a precise mixture of 20.9% oxygen, balance nitrogen (see Table 11) are required to fully 

calibrate the oxygen sensor for maximum accuracy.  
A calibration kit that includes all the required accessories (but not the gas itself) in a convenient carrying case is 
available from Kele.com as part number UCK-1.   The calibration gases are ordered separately using the part 
numbers shown in Table 11. 

All K-O2 sensors include an orificed oxygen sensor calibration-cap stored in the lower left corner of the enclosure 
as shown in 

Figure 10

.  Calibration gas is supplied through the tube-barb flow restrictor fitted to the narrow end of 

the cal cap at a pressure of 10 psi. 

5.2  C

ALIBRATION GAS CONNECTION

 

A schematic of the calibration gas tubing connection between the regulator 
and the calibration cap is shown in Figure 9.  After connecting the 
calibration gas supply hose to the calibration cap, slip the open end of the 
cap over the hexagonal white gas port on the oxygen sensor.  Verify that 
the cap completely covers the gas port; there should be no white showing 
at the bottom of the cap. 

When ready to start the calibration, adjust the calibration gas regulator so 
that the pressure gauge reads 10 psi. 

 

 

 

 

 

Figure 9

: Schematic of Calibration Gas Connection to 

oxygen sensor calibration adapter. 

Type 

Mixture (by volume) 

Kele Part No. 

Zero gas 

Pure nitrogen 

GAS-N2 

Span gas 

20.9% oxygen  

balance nitrogen 

GAS-O2-20.9 

Table 11: 

Required Calibration Gases

 

Figure 10

:  Oxygen sensor calibration cap, 

stored in the lower right of the enclosure 

Summary of Contents for K-O2

Page 1: ...mphis TN 38133 Revision 5 20 2022 www kele com 90 0007 00A K O2 xx Oxygen Sensor Transmitter and Two Stage Alarm Controller User s Manual K O2 H5 5 year sensor K O2 H10 10 year sensor K O2 S5 5 year s...

Page 2: ...ional Description 5 4 1 Special Modes 6 4 2 Warning Ventilation and Alarm Conditions 7 4 3 Setting Ventilation and Alarm Thresholds 7 4 4 Concentration Reporting 7 5 Sensor Calibration 7 5 1 Calibrati...

Page 3: ...sor life K O2 H5 Lockable hinged enclosure with 10 year sensor life K O2 H10 Table 1 K O2 family Part numbers All K O2 xx models are shipped with either 5 year life K O2 x5 or 10 year life K O2 x10 fa...

Page 4: ...ply separate transformer not required Power Consumption 5W Control Relays 2 separate SPDT line voltage capable relays for warning ventilation and alarm outputs UL rated 10 Amps max at 120 277 VAC or 3...

Page 5: ...water entry DO NOT USE THE VENT HOLES FOR WIRE ENTRY 1 This unit is designed to mount to a rigid vibration free surface near the middle of the area to be monitored about 5 feet above the floor 2 It s...

Page 6: ...of the terminal and returns to the terminal The oxygen sensor output is provided at the terminal highlighted in Figure 3 Analog output connection has polarity as labeled on the controller silkscreen...

Page 7: ...to the COM location of screw terminal 5 Plug the relay output screw terminal back into the correct location on controller board 3 3 POWER CONNECTION The K O2 has a fully isolated unpolarized power inp...

Page 8: ...a second contact closure is operated typically to trigger an alarm The gas sensor is a calibrated module that can be replaced with minimal effort when it reaches end of life EOL while leaving the main...

Page 9: ...ormation When the concentration of oxygen falls below its configured warning ventilation threshold the WARNING VENTILATION relay output is activated When the concentration falls below the alarm thresh...

Page 10: ...adequate and requires no calibration gas All that s required is the certainty of fresh air around the sensor For accuracy at lower oxygen percentages a zero calibration before the span calibration is...

Page 11: ...rictor fitted to the narrow end of the cal cap at a pressure of 10 psi 5 2 CALIBRATION GAS CONNECTION A schematic of the calibration gas tubing connection between the regulator and the calibration cap...

Page 12: ...tion gas has been removed the calibration has been applied and the unit is in standby for two minutes while the sensor re equilibrates to the ambient atmosphere before normal operation resumes The cal...

Page 13: ...turns to steady GREEN OR 3B If NOT successful blinking RED The most likely causes of span gas sampling failure are Insufficient gas flow or leaks around the calibration adapter not completely immersin...

Page 14: ...n in To replace a sensor module with a new factory calibrated one follow the steps below 1 Open the controller s front cover 2 Unplug the controllers power connector refer to Figure 6 3 Unplug the sen...

Page 15: ...patible with those Products Unless KELE agrees otherwise to obtain service under this warranty Buyer must pack any nonconforming Product carefully and ship it postpaid or freight prepaid to Kele Inc a...

Page 16: ...tect common failures If a failure is detected the front cover status LED will blink slowly RED the warning relay will be activated and the concentration reporting analog output will stay at 4 mA until...

Reviews: