K-O2 Wiring and Calibration Instructions

Dry contact output

Present on relay 277 V AC,10A

4-20 mA output

Present on analog 
20 mA=>25%
<4 mA => sensor failed

Warning

Alarm

Power 24 V AC/DC

Electrical installation

Always install in accordance with local and national electrical 

• 

codes.  If in doubt about the code requirements of your ap-
plication, consult a licensed electrician.

Both K-O2 enclosure styles have standard ½” conduit knock-

• 

outs on all sides for power and signal wiring.  

Do not use the 

vent openings for wiring.

Power connection

The K-O2 Series of sensors can be powered from 20 to 30 Volts 

• 

AC or DC.  The operating power is connected to the two-posi-
tion screw terminal connector marked “24 VAC/DC” 

K-O2 with  hinged cover

K-O2 with screw cover

K - O 2   C a l i b r a t i o n

A l a r m   S e t t i n g s

 

150.8

5.94  

 

163.5

6.44

 

Conduit Knockout (4 PLS)

Air Vent (2 PLS)

 

 

76.2

3.00

 

 

20.3
0.80

 

 

20.3
0.80

 

76.2

3.00

 

7.9
0.312 (4 PLS)

 

63.5
2.50  

 

76.2

3.00

 

 

63.5
2.50  

 

41.9
1.65  

 

41.9

1.65

 

 

41.9
1.65  

 

52

2.05

 

 

73.7
2.90  

 

20.3

0.80

 

22.2

0.875 (4 PLS)

 

 

 

160

6.30

 

 

147.3

5.80  

Air Vent (2 PLS)

Conduit Knockout (4 PLS)

 

52

2.05

 

 

73.7
2.90  

25.4

1.00

22.2

0.875 (4 PLS)

 

92.7

3.65

 

 

25.4
1.00

 

 

76.2
3.00  

 

76.2

3.00

 

 

41.9

1.65

 

 

35.6
1.40  

7.1
0.281 (4 PLS)

 

76.2
3.00  

 

35.6
1.40  

 

67.310

2.65

 

 

25.400

1.00

 

WARNING /VENTILATION AND ALARM CONDITIONS

Two, 10 Amp, 120/277 VAC rated, dry-contact, SPDT relays activate during 
warning/ventilation and alarm conditions: refer to (Section 3.2 of the Kele 
K-O2 manual)  for wiring information.

When the concentration of oxygen falls below its confi gured warning/
ventilation threshold, the WARNING/VENTILATION relay output is activated. 
When the concentration falls below the alarm threshold, the controller’s 
ALARM relay is also activated. When the oxygen concentration rises above 
the alarm threshold, the ALARM relay is deactivated; when it rises above 
the ventilation threshold the WARNING/VENTILATION relay is also deacti-
vated.

SETTING VENTILATION AND ALARM THRESHOLDS

The four, factory-preset pairs of ventilation and alarm levels are shown in 
Table 6. Each setting determines both the controller’s warning/ventilation 
and alarm thresholds.
The active threshold values are selected by setting the two DIP switches on 
the main board as shown in the fi rst column of Table 6.

SENSOR CALIBRATION

The sensor requires calibration at 
the specifi ed calibration interval to 
ensure its accuracy is maintained 
over its life.  Calibration is a two-step 
process that provides the sensor 
module with oxygen-free (or zero) 
gas, and then a specifi c concentra-
tion (or span) gas.  Two calibration 
buttons (ZERO and SPAN) are pro-
vided on the main board as shown in 
Figure 9.  

FIGURE 9:  Location of SPAN & ZERO Controls

Dip switch 

Setting 

 

OXYGEN % 

 

Warn 

Alarm 

 

20.5  

20.0  

 

20.3 

20.0 

 

20.0 

19.5 

 

19.8 

19.5 

Table 6

POWER

ANAL

OG OUTPUT

O2

+ | -