Front Operation

Time programming

- Press key 

Set

.   The Set label appears.

- Press 

or

 to go to Hour or Minute

- Press 

Set

 to see the value.

- With    and    set the desired new value.
- Press 

Set

. for 8 seconds, Pro will appear on the display once the time has 

been correctly programmed 
-Press 

Set

 and      to quit or wait for 1 minute (keyboard timeout).

Parameter programming
-

 The parameters are grouped in the menus COM, DEF, PRO, ALA, INI, HAC

- Press 

Set

 for 8 seconds.   Value 00 appears blinking.

- Set the code with    and    (it is set to 00 from factory).
- Press 

Set

 to confirm the code. If it is right,   the label of the first menu will 

appear.
-   With    and      go to the desired menu.
- Press 

Set

,   the label of the first parameter of menu will appear.

- With    and      go to the desired parameter label of the list of parameters.
- Press 

Set

 to see the value.

- With    and    set the desired new value.
- Press 

Set

 to confirm it and exit to the parameter label.

-Press 

Set

 +    to go to menu list.

-Press 

Set

 +    to quit programming or wait 1 minute (keyboard timeout).

Date programming

Access to parameter as explained in Parameter programming, select 

INI 

menu and 

dat 

parameter.

- Press key 

Set

.   The day (d00) appears.

- Press 

or

 to go to Day or Month or Year.(d00, M00, Y00)

- Press 

Set

. for 8 seconds, display will blink.

- With    and    set the desired new value.
- Press 

Set

. for 8 seconds, Pro will appear on the display.

To   record   a   standard configuration

- Access to parameter H0 as explained in Parameter programming.

- Press 

Set

 for 8 seconds, and the thermostat will be reset.

Manual Defrost. 

Pressing        key for 8 seconds defrost is activated. Repeating the 
operation  is deactivated.

Continuous cold cycle. 

Pressing           key for 8 seconds a continuous cold cycle begins. 
Repeating the operation the cycle finalizes.

Setting keyboard code to zero

The keyboard code can be programmed to zero by turning off the controller, 
and turning   it on again, while the key 

 is pressed.

Alarm  validation

An active alarm can be validated (the alarm output will be turned off) 
pressing the   

   key. If buzzer is present, it will be muted.

Pressing key         for 5 seconds the thermostat will turn-on or turn-off.

If we have a relay setup as light, pressing key         for 5 seconds the 
thermostat will turn-on or turn-off the light

Pressing

key for 5 seconds the thermostat will turn-on or turn-off

relay setup as

Led Indications

t indicates Compressor connected. It blinks when a 

continuous cold cycle has to be initiated and has to wait until 
the minimum compressor stoppage time is over.

t indicates Compressor 2 connected. It blinks when a 

continuous cold cycle has to be initiated and has to wait until 
the minimum compressor stoppage time is over.

t indicates that a defrost is running

t indicates that fan is connected

t indicates

It indicates HACCP record is activated

  

   

 

  

   

 

EKT82: H0 = 0; EKT83: H0 = 1; EKT84: H0 = 2; EKT85: H0 = 3

Set

Mute

ON/OFF 

ON/OFF Light

 

ON/OFF Aux

 

Aux

  

 the 

 Aux

      

I

       

I

 

          

I

.   
          

I

  

        

I

 error or alarm. It is blinking when the alarm is 

validated for user   

OUT2

OUT2

HACCP

HACCP

-

Display Messages

In   normal operation the probe temperature selected by   P5 will be displayed. The 
following messages can also appear :

 Err

Memory reading error.

-  

ErP1, ErP2, ErP3

Probe1 , 2 or 3   error

Eri

   Internal parameter error. In this case, enter the standard configuration, as it is 

indicated in “To record a standard configuration”.

 

-  ALH

High temperature alarm.

-  ALL

Low temperature alarm.

-  ALE

External alarm.

-  AEH

High temperature and external alarm.

-  AEL

Low temperature and external alarm.

-  ooo     

Open probe.

-   - - -      

Short-circuited probe.

-  DON 

Defrosting activated.

-  DOF 

Defrosting de-activated   or cannot be done.

-  CON 

Continuous cold cycle activated.

-  COF  

Continuous cold cycle de-activated or cannot be done.

-   -d-

Thermostat on defrosting.

-  OFF  

Thermostat OFF.

To view the probe not chosen by P5, press 

Set

+  

The display blinks when there is an error recording a parameter in memory or when 
awaiting confirmation of a value.

Operation in Error Case

If the ambient probe fails, the thermostat will connect the compressor according to 
parameters c2 and c3, being able to perform defrosting and continuous cold cycles.
If the memory fails the thermostat will connect the compressor ON for 5 minutes and 
OFF for 5 minutes, not being able to perform defrosting or continuous cold cycles.

Operation with 2 compressors

In this case when Sd1>=Set+r0 the compressor with less hours of working is turned on 
first and after c6 delay the second compressor is turned on.
When Sd1<Set+r0/2 the second compressor is turned off and when Sd1<Set the first 
compressor is turned off.
If before turning off the first compressor Sd1>=Set+r0 the second compressor is 
turned on again.

HACCP

If this option is activated, the thermostat registers up to 5 alarms of the types High, Low, 
and blackout. These alarms can be seen in the menu Registry of Alarms (HAC). To 
access to this menu, proceed as for the parameters menu. 
The first value that appears is the number of registered alarms. Afterwards, for each 
alarm (if it has existed), the value of the temperature, the time and date (only models 
with real time clock) and elapsed   time of the alarm. For the disconnection alarm, the 
temperature, the time and date (only models with real time clock) when returning the 
connection is registered, as well as the time until the correct values are reached. 
(Probe<Set+A1-A0) 
When the elapsed   time is showed it will appear xxd (days).Pressing      xxH   (Hours) 
will be shown, and pressing    again,   xxn (Minutes) will be displayed. When located 
over a temperature of alarm or time, pressing   +   during 2 seconds, both recorded 
data of the alarm (time and temperature value) are deleted. 
In the HAC menu, and pressing   +     keys during 2 seconds,   all the recorded data of 
alarms are deleted.

Defrosting Cycles

Intelligent Defrosting

By d13 parameter the time between defrost cycles can vary. The time is only counted if 
defrost probe is below the evaporator set d15.
Selecting d13=jup some of the defrosts will be skipped. After a defrost the following 
JdF defrosts will be ignored. JdF is initially 0. If a defrost ends before a time d16*d2 
then JdF is incremented, otherwise is decremented. Maximum value for JdF is 3. 
When JdF is 3 if the next defrost ends before a time d16*d2 then JdF is set to 1, 
otherwise is set to 0.
Selecting d13=Cic the defrosting cycle can vary.
If a defrost ends before a time d16*d2 then time between defrosts is incremented d17 
minutes, otherwise is decremented. The initial and minimum value for time between 
defrost is d8. The number of times that it is incremented it can be seen in JdF.

SLINK

This input allows to connect a programming key to read or to write the parameters.
It also admits a clock module so that the hour of the thermostat goes with a real 
time clock.
If the system is managed with a PC it can be connected it to the thermostat through 
this input with a communication module

The cycles of defrosting can be performed counting total time (d14= rt) or counting 
the time only when the compressor is connected (d14= ct).
If d14= rt, first defrosting will be always made at the hour d3 and the others with the 
cycle given by d8.
If d14= ct, defrosting will be always made with the cycle given by d8.
Manual defrosting do not modify the programmed.

Parameter list

Con Description

Units

Range

Factory       

Set

Set point

Degrees r1 to r2

3.0

r0

Differential or hysteresis

Degrees 0.1 to 20

1.0          

r1

Minimum value for set point

Degrees -99.9 to  r2

-50.0

r2

Maximum value for set point

Degrees r1 to 302

150.0

r4

Night Set Point Variation

Degrees -20.0 to 20.0

0.0

r6

Fan operation 

Range

off /on /con

con

F0

Fan stoppage temperature

Degrees -99.9 to 302

28.0

F1

Fan/compressor stop if door opened Option

no/yes/Con/Fan yes

c0

Minimum compressor stoppage time Minutes

0 to 240

1          

c1

Continuous cycle time

h - m

0.0 to 18

1.0

c2

ON time of fault cycle

Minutes

0 to 999

5

c3

OFF time of fault cycle

Minutes

0 to 999

5

c4

Minimum ON time

Minutes

0 to 240

0

of the compressor

c5

Minimum time between two

Minutes

0 to 240

1

connections of the compressor

c6

Time delay for 2nd compressor   

Seconds 0 to 999

30

DEF Description

Units

Range           Factory 

d0

Type of defrosting 

Range

re /in

re

d1

Temperature at which defrosting

Degrees -99.9 to 302

80.0

          will stop

d2

Maximum defrosting time

Minutes

0 to 240

30

d3

First Hour of Day for Defrosting

h-m

00.0 to 18.0

00.0

d4

Delay of first defrosting

Minutes

0 to 999

0

d5

Display on defrosting

Range

off/on/-d-

-d-

d6

Display return limit.

Minutes

0 to 240

15

d7

Compressor drip time.

Minutes

0 to 240

0

d8

Interval between defrosting

h - m

00.0 to 18.0

8.0

d9

Fan works on defrosting

Range

no/yes

no

d10

Fan drip time

Minutes

0 to 240

0

d11

Minimum Defrosting time 

Minutes

0 to 240

0

d12

Fan/defrosting control probe

Range

sd1/sd2/sd3

sd2

d13

Smart Defrosting

Option

off / jup / Cic

off

d14

Units to count the defrosting cycle

Option

rt / ct

rt

d15

Evaporator set  

Degrees -50.0 to 20.0       -10.0

d16

d2 maximum time %

Numeric 0 to 100

50

d17

CiC time variation

Minutes

0 to 120

10

HdE

Next defrost time(hours)

Hours

(read only)

MdE   

Next defrost time (minutes)

Minutes

(read only)

JdF    

Defrosts to skip

Numeric (read only)

Pro  Description

Units

Range           Factory 

P0

Temperature scale

Option

ºC/ºF

ºC

P1

Ambient probe 1 calibration

Degrees -20.0 to 20.0

0.0

P2

Defrosting probe 2 calibration

Degrees -20.0 to 20.0

0.0

P3

Product probe 3 calibration

Degrees -20.0 to 20.0

0.0

P4

Decimal point

Option

no/yes

yes

P5

Probe to display

Range

sd1/sd2/sd3

sd1

P6

Probe 2 present

Option

no/yes

yes

P7

Probe 3 present

Option

no/yes

no

ALA Description

Units

Range           Factory 

A0

Fan and alarm differential

Degrees 0.1 to 20.0

4.0

A1

Maximum alarm temperature

Degrees 0.1 to 99.9

8.0

A2

Minimum alarm temperature

Degrees 0.1 to 99.9

8.0

A3

 

Minutes

0 to 999

10

A4

Time without temperature alarm after h - m

0.0 to 18.0

1.1

Defrosting

A5

Time without temperature alarm after h - m

0.0 to 18.0

1.1

opening the door

A6

Time without temperature alarm

h - m

0.0 to 18.0

1.1

          after connection

A7

Alarm verification time

h - m

0.0 to 18.0

1.1

A8

Probe  for alarm

Range

sd1/sd2/sd3

sd1

InI  Description

Units

Range           Factory 

Hor

Hour

Hours

0 to 23

0

Min

Minutes

Minutes

0 to 59

0

E0

Configure digital input

Range

off/Al/In/def/rst

off

E1

Configure digital input

Range

off/Al/In/rst

off

H0

Factory Settings 

Range

0 to 3

H1

Master/Slave

Range

Mst / slu

Mst

H2

Keypad protection

Option

no/yes

no

H3

Delay time on connecting

Seconds 0 to 240

0

H4

Address for serial communication

Numeric 0 to 999

0

H5

Keyboard code

Numeric 0 to 999

0

H6

Type of probe

Option

ptc / ntc

ptc

H7

Relay  2 Setup

Option Au/Lit/FAn/ALA/dEF

dEF

H8

Relay  3 Setup

Option Au/Lit/FAn/ALA/dEF

Fan

H9

Relay  4 Setup

Option Au/Lit/FAn/ALA/dEF/Con Lit

H10

Relay  5 Setup

Option Au/Lit/FAn/ALA/dEF

ALA

H11

HACCP Activated   

Option

no/yes

no

dat 

Date

Day/Month/Year

1.1.0

td

Display refresh time

Seconds 0 to 999

0

Some of the parameters may not be present depending on the model.

Digital Input alarm time validation

Hour/Minutes Parameters  H-M 

It is a way to show hours and minutes in 3 digits
The two first digits are the hours and the third the tens of minutes. E.g. 
2.4      2 hours 40 minutes
8.0      8 hours 0 minutes
10.3    10 hours 30 minutes

COMPRESSOR 

c2 

ON time of fault cycle

, when ambient probe is broken

c3 

OFF time of fault cycle

, when ambient probe is broken

Minimum time between two connections of the compressor

(DEF)

Parameter description

 (CON)

SET = Work set point.

Temperature we wish to maintain the machine. Variable between r1 
and  r2.

r0 = Differential. 

When ambient probe temperature >= Set+r0 :   Out ON
When ambient probe temperature <= Set :  Out OFF

r4 = Night Set Point Variation

When the digital input is closed the Set Point is incremented r4. On this purpose 
set E0= rst or E1= rst. 

r6 = Fan operation on regulation.

Off = Fan does not connect on regulation.
On = Fan is always connected on regulation.
Con= Fan linked to compressor start-up.
(Fan ON if allowed by the temperature given by F0)

F0 = Fan temperature limit.

     

 

    

Fan OFF on regulation when probe temperature setup in d12 is   >=   F0.
Fan ON on regulation, when temperature is =<   F0-A0.
The operation of the fan on regulation is determined also by r6.

F1 = Fan stop if door opened. 

On regulation and continuous cycle when opening the door 
No   = The fan and compressor do not stop.
Yes = Both stop.
Con   = The compressor   stops.
Fan = The fan stops.

c0 = Minimum compressor stop time

Minimum   time   since   compressor stops until it is starts again.

c1 = Continuous cycle time.

Duration of a continuous cold   cycle.

c4 = Minimum   time of working of the compressor

Minimum time since compressor starts until it stops.

c5 = 

Minimum   time   since   compressor starts until it starts again.

c6 = Time delay for   2nd Compressor

Time from first compressor is turned on until second compressor is turned on   
(if it is necessary and H9=Con). 

Defrosting 
d0 = Type of defrosting.   

re = defrosting without connecting the compressor.   
in = defrosting by connecting the compressor.

d1 = End of defrosting temperature.   

When this temperature is reached the defrosting will end.

d2 = Maximum defrosting time.

The defrosting will stop when this time is reached.
If it is zero there will be no defrosting.

d3 = first Hour defrosting of the day

From 00:00 hours the first defrosting is at d3 hours.
Until this time no defrosting is performed

d4 = Delay first defrosting. 

Time without defrosting after turning the thermostat on.

d5 = Display during the defrosting. 

Off = The current temperature will be shown during defrosting.
On = The temperature at defrost beginning is frozen on display until the end of 
defrosting and until the current temperature is   equal or lower than the initial 
one, or until d6 time elapses.
def = Label -d- is displayed during defrosting, until the end of defrosting and 
until the current temperature is equal or lower than the initial one, or until d6 
time elapses.

d6 = Display return limit.

Maximum time before viewing   the current temperature again after defrosting.

d7 = Compressor drip time.

Time since defrosting ends until the compressor can be connected.

d8 = Interval between defrosting. 

Time between the start of a defrosting and the start of the following one.
If it is zero defrosting is not done automatically by time.

d9 = Fan operation during defrosting time.

It determines if the fan is connected or not during defrosting.

d10 = Fan drip time.

Time since defrosting ends until fan can be connected.

d11 = Minimum Time duration defrosting

Once defrosting begins it stays at least during this time