Ventilation
If the compressors or condensing units are to be located in machine rooms, adequate ventilation air must be
provided in order to avoid an excessive temperature rise in the room. Air requirements vary with ambient air
temperatures and the refrigeration load, however the following rule of thumb may be used to approximate
ventilating air quantities:
Model Type
Air Quantity
Air-cooled condensing units (for horizontal air flow units)
1,000 cfm (472 L/s) per Hp
Air-cooled compressors (with remote condensers)
250 cfm (118 L/s) per Hp
Suction cooled or water-cooled compressors
200 cfm (94 L/s) per Hp
(with remote or water cooled condensers)
All of the above mentioned air quantities are based on relatively short discharge line runs within the machine
rooms. If using long uninsulated discharge line runs are unavoidable in the machine room, additional ventilation
air is required to offset the heat added to the room by the discharge gas.
Summary of Contents for K40-CU-IM-13
Page 8: ...8 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Page 9: ...9 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Page 10: ...10 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Page 11: ...11 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Page 12: ...12 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Page 13: ...13 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Page 14: ...14 Electrical Wiring Diagram Vertical Air Flow Condensing Units ...