Relay output
Frequency level
Operation of the Unit
The relay output (terminals 1,2,3) is adjusted as a fault relay at the factory.
This parameter can adjust the function of the output to any function listed
in the table below.
Value
Function
0
No function
1
On when unit has voltage applied to it
2
Fault relay
3
No function
4
Overload alert signal (10s before inverter switch off)
5
Over temperature inverter alert signal
6
Over temperature motor alert signal (10s before switch off)
7
No function
8
Stall load level (CP.15) exceeded
9
LA-/LD-Stop load level (CP.14) exceeded
10
DC-braking active
11
No function
12
Load level (CP.3) > 100%
13
No function
14
Actual value=set value (CP.2 = Fcon or rcon only;
not during noP, LS, error, SSF)
15
Acceleration (CP.2 = FAcc, rAcc, LAS)
16
Deceleration (CP.2 = FdEc, rdEc, LdS)
17
Forward rotation (not during noP, LS error)
18
Reverse rotation (not during noP, LS error)
19
Actual direction of rotation = set direction of rotation
20
Actual frequency > frequency level CP.23
21
Set frequency > frequency level CP.23
22
No function
23
Operating signal (active after initialization; off when fault occurs)
24
Run signal
25
No function
Factory setting:
2
Note:
Enter-Parameter
Customer adjustment:
_______
This parameter determines the switching point for the relay output
terminals 1,2,3 when CP.22 = "20” or “21”
After the switching of the relay, the frequency can move within a 0.5 Hz
window, without the relay changing states.
Adjustment range:
0.0...409.58 Hz
Resolution:
0.0125 Hz
Factory setting:
4 Hz
Customer adjustment:
_______