Electrical installation
Operation Manual ServoOne CM-L and ServoOne CM-A
ID no.: 1800.208B.1-00 Date: 03/2020
Electrical installation
4.11.2 Specification, connection "State" (X6)
Des.
Abbreviation
Specification
Details
X6/State
RO01NC = normally
closed contact
RO01CO = changeo-
ver contact
RO01NO = normally
open contact
RO01NC
RO01CO
RO01NO
Relay contact:
≤
50 V AC, 0.5 A max. (ohmic
load)
contact freely programmable
Factory setting = Active on error
TP00 =
test pulse signal 00
TP01 =
test pulse signal 01
GND =
reference ground
Signal driver outputs for in-
ternal usage for short-circuit
and cross-circuit checks on
the wiring to the safe inputs
on the axis controllers
See
Model Description SD0
ID no. 1400.402B.x-xx
EXP–
EXP+
Quick shutdown, mains
output.
If there is an error in the axis
group SO CM (BG1+2), the
expansion module sends a
quick shutdown signal to the
SO CM-A.
The cable to the expansion
module SO CM-E is connect-
ed to this connector.
x
Quick shutdown
(emergency shutdown)
x
Two-core cable
x
Polarity reversal protection
x
Cross-section: max.
1.5 mm
2
without ferrules
x
Max. 6 bus users
GND
PF
Power failure
Signals power failure with a
24 V signal
4.11.3 Specification, relay contact (X5)
Des.
Abbreviation
Specification
Details
X5/REL Output
RO02NO
= normally
open
contact
RO02CO
RO02NO
Relay contact: 230 V AC, 4 A
max. (ohmic load),
contact freely programmable
Factory setting = Operation of
main contactor
Key to the layout, ServoOne CM-L charging module
Item
Abbrevia-
tion
Designation
Details
LED red
(ERR)
LED green
(Voltage)
Supply unit error status (flashing
code)
Status mains supply available
See Section 5.1.1
X3
XC OUT
Cross-communication
See Section 4.11.1 Specification,
X6
State
Relay contact (RO01)
Digital outputs (TPO0, TPO1)
Quick shutdown EXP-/EXP+
Power failure PF
See Section 4.11.2
Specification, connection "State" (X6)
X5
REL
Output
Relay contact (RO02)
See Section 4.11.3
Specification, relay contact (X5)
X1
ϑ
1
, ϑ
2
Connection for mains filter (
ϑ
1
) and
mains choke temperature sensor
(
ϑ
2
)
See “4.11.4 Specification, connection of
X1
BR,
ϑ
Connection for braking resistor
temperature sensor
See Section 4.11.4 Specification, connec-
tion of temperature sensor (X1)
-
Shield plate
Table 4.16
Key to layout, control connections ServoOne CM-L charging module
4.11.1 Specification, cross-communication (X3)
Des.
Abbreviation
Specification
Details
X3
XC OUT
Cross-communication output (RJ10
connector), internal RS485 network for
communication with axis controllers
See
Operation Manual SO CM
ID. no. 1800.200B.x-xx