47
cONNecTION Of THe POWer UNIT
4.2.5.4 Motor cable length for parallel operation of motors
The resulting motor cable length for parallel operation of motors, or parallel installation
with multiple cables arises from the following formula:
resulting motor cable length = ∑single line length x √
Number of motor lines
4.2.5.5 Motor cable cross-section
The motor cable cross-section is dependent
• on the characteristic of the output current (e.g. not sine-wave).
• on the real effective value of the motor current.
• on the cable length.
• on the type of the used cable.
• on the ambient conditions such as bundling and temperature.
4.2.5.6 Interconnection of the motor
NOTICE
Protect motor against voltage peaks !
Drive converters switch at the output with du/dt ≤ 5kV/µs. Voltage peaks
that endanger the insulation system at the motor can occur especially in
case of long motor cables (> 15 m). A motor choke, a dv/dt-filter or sine-
wave filter can be used for protection of the motor.
The connecting-up instructions of the motor manufacturer are always
generally valid !
4.2.5.7 Terminal strip X1B motor connection
X1b
Name
function
R -- ++ U V W
U, V, W Motor connection
Type
Push-In spring connection
Screwdriver blade
08 x 4.5
Stripping length
12 mm
Wire cross-section
AWG 24-8
without wire-end ferrule
0.5...10 mm²
with wire-end ferrule
1.5...6 mm²
Figure 16:
Terminal strip X1B motor connection