3.1.4 electrical operating conditions
3.1.4.1
Device classification
requirement
Standard
class
Descriptions
Overvoltage category
III
–
–
Pollution degree
2
Non-conductive pollution, occasional conden-
sation when PDS is out of service
Table 5:
Device classification
3.1.4.2 Electromagnetic compatibility
An external filter is required for devices without an internal filter in order to comply with
the following limits.
eMc emitted interference
Standard
class
Descriptions
Conducted emissions
C2
–
Radiated emissions
C2
–
Immunity
Standard
Level
Descriptions
Static discharges
8 kV
4 kV
AD (air discharge)
CD (contact discharge)
Burst - Ports for process
measurement control lines
and signal interfaces
2 kV
–
Burst - Power ports
4 kV
–
Surge - Power ports
1 kV
2 kV
Phase-phase
Phase-ground
Immunity to conducted distur-
bances, induced by radio-fre-
quency fields
10 V
0.15...80 MHz
Electromagnetic fields
10 V/m
3 V/m
1 V/m
80 MHz...1 GHz
1.4...2 GHz
2...2.7 GHz
Voltage fluctuations/
voltage dips
–
-15 %...+10 %
90 %
Frequency changes
–
≤ 2 %
Voltage deviations
–
±10 %
Voltage unbalance
–
≤ 3 %
Table 6:
Electromagnetic compatibility