Page 3.6 - 4
COMBIVERT R6-N
© KEB, 2015-07
Protection functions
Unit of the pre-warning
Pre-warning period or level adjustable
Pre-warning possible via digital output
Function can be switched off
Automatic restart adjustable
Error without adjustable response
Message
Operator
values Message COMBIVIS
E.buS/ A.buS
18/93
Error!/warning! Watchdog
- • • - •
s
E.EEP
21
ERROR! EEPROM defective
• - - - -
-
E.EF/ A.EF
31/90
Error!/warning! ERROR external fault
- • • - -
-
Error !
15
ERROR! Load shunt fault
• - - - -
-
E.nEt
3
ERROR! Mains
• - - - -
-
E. OC
4
ERROR! Overcurrent
- • - - -
-
E.OH/ A.OH
8/89
Error!/warning! Power module temperature
- • - • • °C
E.OHI/ A.OHI
6/87
Error!/warning! Interior temperature
- • • • •
s
E.OL/ A.OL
16/99
Error!/warning! overload (Ixt)
- • - • • %
E. OP
1
ERROR! Overvoltage
- • - - -
-
E. Pu
12
ERROR! defective in power unit
• - - - -
-
E.Puch
50
ERROR! Power unit code changed
• - - - -
-
E.Puci
49
ERROR! Power circuit unknown
• - - - -
-
Error: Power
circuit identi-
fication was
changed;
14
ERROR! power unit coding
• - - - -
-
E.SEt/ A.SEt
39/102
Error!/warning! Set
- • • - -
-
E.SYn
59
ERROR! Synchronization
• - - - -
-
E. UP
2
ERROR! Undervoltage
- • - - -
-
F.nEt
40
ERROR! mains frequency
• - - - -
-
3.6.1.1 Undervoltage
"Error ! Undervoltage "(E.UP) is triggered if the DC link voltage drop due to voltage dip or generally at low net-
work. The automatic restart can be activated for this error.
3.6.1.2 Overvoltage
"Error ! Overvoltage" is triggered if the DC link voltage increases beyond the overvoltage level.
3.6.1.3 Overcurrent
The "Error! Overcurrent“ (E.OC) is triggered, if the „OC tripping current“ (see technical data in the instruction
manual) is exceeded.
If this error occurs permanently, either the parameter setting is not correct or the COMBIVERT is defective.
Summary of Contents for COMBIVERT R6-N
Page 2: ...Page1 1 2 COMBIVERT R6 N KEB 2015 07 Introduction ...
Page 4: ...Page1 1 4 COMBIVERT R6 N KEB 2015 07 Introduction ...
Page 14: ...Page1 2 6 COMBIVERT R6 N KEB 2015 07 Product overview ...
Page 28: ...Page2 1 6 COMBIVERT R6 N KEB 2015 07 Fundamentals ...
Page 34: ...Page2 2 6 COMBIVERT R6 N KEB 2015 07 Password input ...
Page 40: ...Page3 1 2 COMBIVERT R6 N KEB 2015 07 Parameter summary 3 1 1 Parameter list R6 N 3 1 3 ...
Page 128: ...Page 3 9 10 COMBIVERT R6 N KEB 2015 07 Define CP Parameters ...
Page 136: ...Page 4 1 8 COMBIVERT R6 N KEB 2015 07 Preparatory measures ...
Page 146: ...Page 5 1 6 COMBIVERT R6 N KEB 2015 07 Error Diagnosis ...
Page 156: ...Page 7 1 2 COMBIVERT R6 N KEB 2015 07 Appendix 7 1 1 Index 7 1 3 ...