GB - 11
Only Qualified
Personnel
Danger to Life
Observe
Standards
Installation
3
Transport and Storage
The storage of the R4-S-regenerative unit must be done in its original packing.
Protect the R4-S regenerative unit against moisture and cold and warm effects.
The transport over long distances must be done in the original packing. Protect
the R4-S-feedback against impact load.
Please note the identifying marking at the packing!
After removing of the packing for the installation the R4-S-regenerative unit must
stay on a steady base.
4
Installation
Installation and start-up of the R4-S-regenerative unit is only allowed by qualified
personnel. Safe and trouble-free operation is only possible with the following
standards: DIN VDE 0100, DIN VDE 0113, DIN VDE 0160, DIN VDE 0875 and
other relevant local conditions. The unit must be earthed via the protective
conductor. The power terminals L1_2, L2_2 and L3_2 and the terminals for
synchronization (L1, L2, L3) must be executed with shielded lines.
Attention, the terminals L1, L2, L3, and -IN, -OUT, +OUT, +IN and L1_2, L2_2,
L3_2 do have high dangerous voltages when they are ON!
All installation and connection work must be done in a off circuit status!
A view minutes after switching off the D.C.-bus of the R4-S-regenerative unit
has a high voltage. Working at the unit is only allowed after 5 minutes.