35
Control circuit
4.3.5.3 Temperature inputs
U
R1+
R1-
Input type
Pt100
Connection
two-wire
Measuring range
-40…+80 °C
Terminals
R0+…R3+ X2A.10/12/14/16
R0-…R3- X2A.9/11/13/15
Figure 23: Temperature inputs
Attention
The inputs are not electrically isolated to the control board, so
that a motor temperature detection must not connected!
Motor temperature measurement see chapter 4.2.3.3.
4.3.5.4 Analog inputs
The analog inputs are optional.
AI0+, AI1+
AI0-,AI1-
I
Differential inputs
AI 0, AI 1
Specification
U/I: selectable:
0…±10 V(Ri=55 kΩ)
0…±20 mA (Ri=250 Ω)
4…20 mA (Ri=250 Ω)
Resolu-
tion:
11 Bit + sign
Terminals
AI0+/AI1+ X2A.6/ 8
AI0-/AI1- X2A.5/ 7
Figure 24: Analog inputs
4.3.5.5 Relay output
RLA
RLC
Output
RLA, RLC
Specification
U: max. 30 Vdc
I: 0.01…1 A
Terminals
RLA X2A.1
RLC X2A.2
Max. number of
switching cycles
10
8
mechanical;
500.000 at 30 V/1 ADC
Others
only ohmic load, respec-
tively inductive load with
corresponding protective
wiring
Figure 25: Relay output