28
Power unit
4.2.3.3 Motor temperature detection, terminals T1, T2
The KEB COMBIVERT P6 has a switchable KTY84/PTC evaluation. The input has „basic
insulation“ to the supply respectively to the „protective separation voltage“ ! The desired func
-
tion is set with dr33 and works according to the following table:
dr33 Function of T1, T2
Resistance
Display ru28
0
KTY84
(standard)
< 330 Ω
Short circuit
359
Ω
-40°C
1 kΩ
100°C
1.722 kΩ
200°C
> 1800 Ω
Open circuit
1
PTC
(according
DIN EN 60947-8)
< 750 Ω
PTC closed
0.75…1.65 kΩ (reset resistance)
undefined
1.65…4 kΩ (tripping resistance)
undefined
> 4 kΩ
PTC open
Table 3:
Temperature monitoring with KTY or PTC
Info
KTY or PTC cable inside the motor cable only permissible with double
shielding !
Info
Do not lay KTY or PTC cable of the motor (even shielded) together
with control cable !
T1
T2
+
KTY84
M
KTY sensors are poled semiconductors and must
be operated in forward direction! Connect anode
to T1 ! Non-observance leads incorrect measure
-
ment in the upper temperature range. Protection
of the motor winding is no longer guaranteed.
Figure 14: Connection of a KTY sensor
4.2.4 Brake control
4.2.4.1 Control of a 24 Vdc brake
Terminal block X1B
Name
Description
B+
B-
U=24Vdc
B+
24 V/ max. 4.2 Adc output for direct
brake control.
A free-wheeling di-
ode is internally installed.
B-
Figure 15: Connection of a 24 Vdc brake