Quick Start with a TEV

  

Power up the newly installed controller

  The 

ROOM TEMP

 display will show a blinking number. Use the 

left or right arrow to move between digits, use the up or down 

arrow to adjust the blinking digit higher or lower.

  Once new setpoint is displayed, press and hold ENTER for 3 

seconds

  Now, the

 DEFROST TYPE

 is displayed. Wait until

 ELEC

 (Electric 

Defrost) is displayed, if other than ELEC is needed, use the up 

or down arrow to scroll through list and select 

AIR, HOT GAS 

COMP ON, HOT GAS COMP OFF

  Once desired option is shown, press and hold ENTER key for 3 

seconds.

  

VALVE TYPE

 is displayed. 

MECHANICAL

 will appear.

  Press and hold ENTER for 3 seconds.

  The controller will now begin controlling the system.

Quick Start with a Custom EEV

  

Power up the newly installed controller

   The 

ROOM TEMP

 display will show a blinking number. Use 

the left or right arrow to move between digits, use the up or 

down arrow to adjust the blinking digit higher or lower.

  Once new setpoint is displayed, press and hold ENTER for 3 

seconds

   Now, the 

DEFROST TYPE

 is displayed. Wait until 

ELEC

 (Elec-

tric Defrost) is displayed, if other than 

ELEC

 is needed, use the 

up or down arrow to scroll through list and select 

AIR, HOT 

GAS COMP ON, HOT GAS COMP OFF

   Once desired option is shown, press and hold ENTER key for 3 

seconds.

  

VALVE TYPE

 is displayed. 

MECHANICAL

 will appear, use the 

up or down arrows to scroll to 

CUSTOM

.

   Press and hold ENTER for 3 seconds.

  

REFRIGERANT 

is displayed. 404A will appear. Use the up or 

down arrows to view the other options. 

 Once the desired refrigerant is displayed, press and hold ENTER 

for 3 seconds.

  

MOTOR TYPE

 is displayed. Wait until 

BIPOLAR

 is displayed. 

Use the up or down arrows to select either 

BIPOLAR

 or 

UNI-

POLAR 

   Press and hold ENTER for 3 seconds.

  

MOTOR STEP RATE

 is displayed. Wait until 

200

 is displayed. 

Use the left and right arrows to move between the digits. Use 

the up or down arrows to adjust the blinking digit higher or 

lower.

   Press and hold ENTER for 3 seconds.

  

MAX VALVE STEPS 

is displayed. Wait until 

1300

 is displayed. 

Use the left or right arrows to move between digits. Use the 

up or down arrows to adjust the blinking digit higher or lower.

   Press and hold ENTER for 3 seconds.

   The controller will now begin controlling the system.

Quick Start with a Pre-programmed EEV

  

Power up the newly installed controller

  The 

ROOM TEMP

 display will show a blinking number. Use 

the left or right arrow to move between digits, use the up or 

down arrow to adjust the blinking digit higher or lower.

  Once new setpoint is displayed, press and hold ENTER for 3 

seconds

  Now, the 

DEFROST TYPE 

is displayed. Wait until 

ELEC

 (Electric 

Defrost) is displayed, if other than ELEC is needed, use the up 

or down arrow to scroll through list and select 

AIR, HOT GAS 

COMP ON, HOT GAS COMP OFF

  Once desired option is shown, press and hold ENTER key for 3 

seconds.

  

VALVE TYPE

 is displayed. 

MECHANICAL

 will appear, use the 

up or down arrows to scroll through pre-programmed EEV op-

tions. 

  Once the desired EEV is displayed, press and hold ENTER for 3 

seconds.

  

REFRIGERANT

 is displayed. 404A will appear. Use the up or 

down arrows view the other options. 

  Once the desired refrigerant is displayed, press and hold EN-

TER for 3 seconds.

  The controller will now begin controlling the system.

Step-by-Step QuickStart

Mechanical Valve TEV - 

3 steps

Standard EEV - 

4 steps

Custom EEV - 

7 steps

Room Temp  

Room Temp  

Room Temp  

Defrost Type

Defrost Type  

Defrost Type

Valve Type  

Valve Type

Valve Type  

Refrigerant  

Refrigerant  

Motor Type (Unipolar/Bipolar)

Motor Step Rate
Max Valve Steps  