V1.00
multisys D2-MSMT
20742_EDEBD
A0231-2516-1_EN
11
Example:
Modbus/TCP to RTU Bridge
MAC address 0080A3A77528
Software version V3.3.0.5 (140827) XPTE
Press Enter for Setup Mode
Model: Device Server Plus+! (Firmware Code:YM)
Modbus/TCP to RTU Bridge Setup
1)
Network/IP Settings:
IP Address .............................................. 192.168.0.1
Default Gateway ................................. --- not set ---
Netmask ................................................. 255.255.255.0
2)
Serial & Mode Settings:
Protocol .................................................. Modbus/RTU, Slave(s) attached
Serial Interface ..................................... 19200,8,E,1,RS485
3)
Modem/Configurable Pin Settings:
CP1 ........................................................... RS485 Output Enable
CP2 ........................................................... Not Used
CP3 ........................................................... Not Used
4)
Advanced Modbus Protocol settings:
Slave Addr/Unit Id Source ............... Modbus/TCP header
Modbus Serial Broadcasts ............... Disabled (Id=0 auto-mapped to 1)
MB/TCP Exception Codes ................ Yes (return 00AH and 00BH)
Char, Message Timeout .................... 00050msec, 05000msec
7)
Security Settings:
SNMP ...................................................... Enabled
SNMP Community Name ................. public
Telnet Setup ......................................... Enabled
TFTP Download ................................... Enabled
Port 77FEh ............................................. Enabled
Web Server ............................................ Enabled
Enhanced Password .......................... Disabled
Port 77F0h ............................................. Enabled
D)efault settings, S)ave, Q)uit without saving
Select Command or parameter set (1..7) to change:
You can now change the settings and save them by pressing
S
.
You can now operate the device with the new network parameters.
Configuration via Ethernet interface