Rev. 2.01
22070_EDEBD
A0241-3617-1_EN
7
KBR multisio D2-4AI-2
5
Scan button function
NOTE
If the scan button is pressed briefl y,
the module enters the scan mode.
Illustrated switch setting:
OFF = white
ON = gray
6
DIP switch function
Switching inputs 1 to 4:
Switch set to
OFF:
Switch set to
ON:
S1 = 0 / 2 – 10V S1 = 0 / 4 – 20mA
S2 = 0 / 2 – 10V S2 = 0 / 4 – 20mA
S3 = 0 / 2 – 10V S3 = 0 / 4 – 20mA
S4 = 0 / 2 – 10V S4 = 0 / 4 – 20mA
Scan-Button
Scan-Taster
DIP-Switch
DIP-Schalter
ON SAB
1 2 3 4
ON SAB
1 2 3 4