V2.01
25359_EDEBD
A0279-2320-1_EN
14
Control and display panel
4
Setting Range of the Configurable Parameters:
Stage state:
Stage switching mode
Automatic, Manual off, Manual on
Commissioning:
Password
4 digits, numerical, no password = 9999
(meaning all functions are accessible)
Primary current
1 A to 999999 A
Secondary current
1 and 5 A
Consumption target cosφ
ind. 0.80 to cap. 0.80
Recovery target cosφ
ind. 1.0 (cannot be changed)
Primary voltage
1 V to 99999 V Ph-Ph
Secondary voltage
1 V to 999 V Ph-Ph
Rot. field U
L1N, L2N, L3N, L12, L23, L31
Rot. field I
L1, L2, L3, -L1, -L2, -L3
Stage power learning mode
Yes, No
Stage power
0 to 999.9 kvar
Discharge time
0 to 999 sec.
Switching performance:
Hysteresis connection
70 to 150 %
Hysteresis switch-off
70 to 150 %
Switching performance Priority
Operation cycles, runtime
Alarm relay time
3 to 3000 sec.
Idle time
0 to 300 sec.
Switching interval
0 to 10 sec.
FTS alarm cosφ
ind. 0.70 to 1.0
Attenuation coefficient Qmiss
0 to 9
Attenuation coefficient voltage
0 to 9
Attenuation coefficient current
0 to 9