Rev. 1.00
22585_EDEBD
A0252-0318-1_EN
29
KBR multicomp F144-3 6DO/12DO
Description of the display window
This is displayed after the initialization window if the stage power has already
been configured. The current total controller state and the currently measured
CosPhi are measured here.
Example:
Line 1: currently measured CosPhi 0.71 inductive
Line 2: the controller switches on stages; stages 1 to 4 are already switched to
automatic operation, where:
stages are switched on as compensation power is required.
stages are switched off due to overcompensation.
A
the stage has been switched to automatic mode.
H
the stage has been switched on manually.
0
the stage has been switched off manually.
X
the stage's measured stage power does not correspond to the con-
figured value (stage monitoring activated, see the Stage monitoring
submenu of the Extras menu).
Press
W
to select submenus.
cos 0.71 IND
AAAA
The controller should start automatically after it is reconnected to the power
supply. If the cos
φ
voltage is read in the start menu immediately after switching
it on, the value for cos
φ
should be low and inductive. The controller then starts
to switch on the individual capacitor stages.
The cos
φ
, which can be read in the start menu, should have risen in comparison
to its previous value, or it should rise when additional stages are switched on. If
the compensation system is designed correctly, the controller should compen-
sate to the set target cos phi after a while.