Connection
Basic system parameters switching performance:
Hysteresis connection
100% of lowest stage power
Hysteresis switch-off
100% of lowest stage power
Alarm delay
1200 seconds (20 minutes)
Idle time:
10 seconds
Switching interval:
8 seconds
Current attenuation coefficient:
2
Voltage attenuation coefficient:
2
Attenuation coefficient Qmiss:
2
Basic system temperature parameters:
Measurement
active
Switching thresholds
Fan switched on
28°C
Fan switched off
23°C
Stages switched on
43°C
Stages switched off
48°C
Basic system limit parameters:
Operating cycle limit
80000 connections
Operating cycle count
Activated by set limit
Overvoltage limit
440 VAC PhPh (corresponds to 10 %)
Current low load limit
10 A
Average current limit:
6-Fold current
transformer ratio
Limit THD
8%
Activated by set limit
Limit Id
20 %
Harmonics monitoring
Activated by set limit