KBR multimess D9-PQ
20144 EDEBD
A0228-5023-1_EN
55
6.4.5
Oscilloscope recorder
Settings for Oscilloscope recorder can be changed here.
Minimum recorder length: Setting of the standard faultrecorder length
Maximum recorder length: If one fault last longer than the minimum recorder
length, the multimess D9-PQ will enlarge the recorder length up to a maxi-
mum recorder length. The maximum recorder length of one recorder file can
be set here.
Recorder pretime is the time of the recorder file bevore the trigger threshold
occurred.
pretime
threshold
recorder posttime
active
passive
Active trigger = value exceeds or falls below threshold (start of the event)
Passive trigger = value comes back to normal (end of the event)
Sampling frequency of oscilloscope recorder can be changed from 10240 Hz
to 40960 Hz (40960Hz is only available with option B1)
Sampling frequency: 40960Hz / 10240Hz
40960
40960
10240
40960
Software WinPQ smart