WARnInG! The signal input must be isolated from the AC line. Earth grounding
signal wiring will damage the drive and void the warranty. It is recommended that
the SIVfR — Signal Isolator and Run/fault Relay (Part no. 9597) be installed when
using signal following.
9.6
Manual Start Switch Connection
(COn1) –
The Manual Start Mode is
used to manually start the drive or
restart the drive (reset) if a fault has
occurred. To operate the drive in
the Manual Start Mode, remove the
factory installed jumper on CON1
and install the 2-wire connector
(supplied). CON1 is located on the
lower PC board. The connector
must be wired to a momentary
switch or contact, as shown in
Figure 19.
In the Manual Start Mode, the drive will trip due to all faults (Overvoltage, Undervoltage, Short
Circuit, and I
2
t) and remain tripped even when the fault is cleared. To Start/Reset the drive, the
switch or contact must be manually closed. Also, the drive must be restarted each time the
AC line is interrupted.
For
Automatic Start
, see Section 6.3, on page 26.
Notes: 1.
See Section 11.2, on page 35. Also see Section 12.2, on page 38.
2.
The drive can
be factory programmed for Run/Stop operation with momentary contacts.
33
FIGURE 19 – MANUAL START SWITCH CONNECTION
Jumper Removed
Connector Installed for
Manual Start Switch
CON1
A/M
Manual Start Switch
(Momentary Contacts)
(Push to Run)
White
Black
CON1