6

SETTING SELECTABLE JUMPERS

The drive has customer selectable jumpers which must be set before the drive can be used.  For the location of jumpers, see 

Figure 4, on

page XX

.

6.1

AC Line Input Voltage Selection (Jumper J1 (Models KBVF-21D, 22D, 23D, 24D, 26D* Only)): Jumper J1 is factory set to the
"230V"  position  for  208/230  Volt  AC  line  input.    For  115  Volt  AC  line  input,  set  Jumper  J1  to  the  "115V"  position.    Jumper  J1  is
located on the upper PC board.  See 

Figures 7 and 8, on page XX

.

For  115  Volt  AC  line  input,  on  Model  KBVF-26D,  the  jumper  must  be  removed  and  installed  onto  the  "115VAC"  position.    Using
pliers, gently rock the female terminal back and forth vertically while pulling it upward.  See 

Figure 9, on page XX

.

* Note: On Model KBVF-26D, Jumper J1 is labeled "115VAC" and "230VAC".

Figure 7

Models KBVF-21D, 22D, 23D, 24D

AC Line Input Voltage Selection

230 Volt AC Line Input

(Factory Setting)

(J1 Installed in "230V" Position)

115 Volt AC Line Input

(J1 Installed in "115V" Position)

Figure 8

Model KBVF-26D

AC Line Input Voltage Selection

Figure 9

Removing Jumper J1

on Model KBVF-26D

230 Volt AC Line Input

(Factory Setting)

(J1 Installed in "230VAC" Position)

115 Volt AC Line Input

(J1 Installed in "115VAC" Position)

6.2

60Hz and 50 Hz Motor Operation and Drive Output Frequency Selection (Jumpers J1 and J2): Both jumpers must be set for
the appropriate motor nameplate frequency rating.  Jumpers J1 and J2 are located on the lower PC board.

6.2.1

Setting the Drive for 60 Hz or 50 Hz Motor  Operation: The  drive  is factory  set to  operate  60  Hz motors.   Jumper  J1  is
factory set to the "60Hz" position and Jumper J2 is factory set to the "X1" position.  For 50 Hz motors, set Jumper J1 to the
"50Hz" position, and be sure Jumper J2 is set to the "X1" position.  Jumpers J1 and J2 are located on the lower PC board.
See 

Figure 10, on page XX

.

Figure 10

60 Hz and 50 Hz Motor Selection

60 Hz Motor Operation

(Factory Setting)

(J1 Installed in "60Hz" Position)

(J2 Installed in "X1" Position)

50 Hz Motor Operation

(J1 Installed in "50Hz" Position)

(J2 Installed in "X1" Position)

6.2.2

Setting the Drive for Two Times the Rated Motor RPM: The drive can also be used to operate the motor up to two times
the  rated  RPM.   However,  constant  horsepower  will  result  when  operating  the  drive  in the  "X2" mode.   See 

Figure  11,  on

page XX

.

For 120 Hz output with 60 Hz motor, be sure Jumper J1 is set to the "60Hz" position and set Jumper J2 to the "X2" position.
For  100  Hz  output  with  50  Hz  motor,  set  Jumper  J1  to  the  "50Hz"  position  and  set  Jumper  J2  to  the  "X2"  position.    See

Figure 12, on page XX

.

Summary of Contents for KBVF-21D

Page 1: ...is manual covers Models KBVF 21D 22D 13 23 23D 14 24 24D 26D Note The drive is factory set for 60 Hz motors For 50 Hz motors see Section 6 2 on page XX The information contained in this manual is inte...

Page 2: ...Model KBVF 26D AC Line Input Voltage Selection XX 9 Removing Jumper J1 on Model KBVF 26D XX 10 60 Hz and 50 Hz Motor Selection XX 11 Available Torque vs Output Frequency XX 12 120 Hz and 100 Hz Drive...

Page 3: ...line voltage of the drive must match the actual AC line input voltage On Models KBVF 21D 22D 23D 24D 26D the setting of Jumper J1 on upper PC board must match the AC line input voltage Models KBVF 13...

Page 4: ...counterclockwise WARNING The signal input must be isolated from the AC line Earth grounding signal wiring will damage the drive and void the warranty It is recommended that the SIVFR Signal Isolator...

Page 5: ...ne Voltage dual voltage models only Automatic Manual Start Motor Frequency Frequency Multiplier Forward Reverse Diagnostic LEDs are provided for power PWR and drive status ST A 5 k Main Speed Potentio...

Page 6: ...ard Part No 9503 Provides multi speed operation using external contacts or a PLC Mounts on the end of the drive Programming Kit Part No 9582 Includes DownLoad Module DLM handheld programming device wh...

Page 7: ...24 24D 2 5 7 5 6 4 Current Limit Trimpot CL Range Amps AC KBVF 26D 3 5 10 5 8 8 Motor Frequency Setting Hz Jumper J1 50 60 60 Output Frequency Multiplier X1 X2 Jumper J2 2 1 2 1 Minimum Operating Freq...

Page 8: ...e Some fan cooled motors can be used over a wider speed range Consult the motor manufacturer for details WARNING Some motors have low speed characteristics which cause overheating and winding failure...

Page 9: ...l contact with high voltage WARNING Disconnect main power when removing or installing the Finger Safe Cover WARNING To prevent accidental contact with high voltage it is required that the Finger Safe...

Page 10: ...D 230 Volt AC Line Input Factory Setting J1 Installed in 230VAC Position 115 Volt AC Line Input J1 Installed in 115VAC Position 6 2 60Hz and 50 Hz Motor Operation and Drive Output Frequency Selection...

Page 11: ...jumper installed in the F position of CON2 CON2 is located on the lower PC board For reverse Speed Operation install the jumper in the R position See Figure 14 on page XX To wire a Forward Stop Rever...

Page 12: ...ING INSTRUCTIONS WARNING Read Safety Warning on page XX before using the drive Disconnect main power when making connections to the drive To avoid electric shock be sure to properly ground the drive A...

Page 13: ...PC board See Figure 17 on page XX WARNING Do not earth ground any Main Speed Potentiometer terminals Figure 17 Main Speed Potentiometer Connection Note When mounting the Main Speed Potentiometer be su...

Page 14: ...can be factory programmed for Run Stop operation with momentary contacts Figure 19 Manual Start Switch Connection Jumper Removed Connector Installed for Manual Start Switch 9 7 Forward Stop Reverse S...

Page 15: ...covery The drive monitors for four faults Undervoltage Overvoltage Short Circuit at the motor phase to phase I2 t Table 3 on page XX describes how the drive will automatically start factory setting af...

Page 16: ...Quick Flash 0 25 second on and 0 25 second off 2 In Manual Start Mode when the Overload is removed before the I 2 t times out and trips the drive the ST LED will flash green 3 In Manual Start Mode wh...

Page 17: ...increase in time This will slow down the rate of speed of decrease to prevent the bus voltage from rising to the Overvoltage Trip point This function is called Regeneration Protection It is recommend...

Page 18: ...eters do not provide accurate readings 2 Run the motor unloaded at approximately 4 Hz or 120 RPM Note An unloaded motor with excessive boost will draw more current than a partially loaded motor 3 Incr...

Page 19: ...7 A40288 Rev E 6 6 2005 Z3562E00 Page 19 of 20 Figure 28 Model KBVF 21D Current Limit Trimpot CL Range Figure 29 Model KBVF 22D Current Limit Trimpot CL Range Figure 30 Models KBVF 13 23 23D Current L...

Page 20: ...ied The foregoing is in lieu of any other warranty or guarantee expressed or implied KB Electronics Inc is not responsible for any expense including installation and removal inconvenience or consequen...

Reviews: