KB Electronics 9646 Installation And Operation Instructions Download Page 4

IODF INPUT/OUTPUT MULTI-FUNCTION EXPANSION MODULE KIT (PART NO. 9646) 

INSTALLATION AND OPERATION INSTRUCTIONS 

 

 

 KB 

Electronics, 

Inc. 

 

12095 NW 39th Street, Coral Springs, FL 33065-2516 

 (954) 346-4900 

 FAX (954) 346-3377 

 

Outside Florida Call Toll Free (800) 221-6570 

 [email protected] 

 www.kbelectronics.com 

Page 4 of 4  

(A40193) – Rev. A00 – 5/7/2013

 

Other Programmable Functions of the Multi-Function Output Relay (Function 5.01) 
Code   Description 

0000:  

Run 

0001:  

Fault 

0002:  

Target Frequency (Function 5.03 ± Function 5.04) 

0003:  

Frequency Threshold Level (>Function 5.03 –  Function 5.04) 

0004:  

Frequency Threshold Level (<Function 5.03 +  Function 5.04) 

0005:  

I

2

t or I•t Fault 

0006:  

Load Loss (See Function 5.05) 

0007:

   External  Fault 

 

 
 

3.3 ANALOG INPUT 

Connect the 0-2.5 thru 0-25 Volt DC signal input to Terminal "18" and the common to Terminal "19". Connect  the Start (Jumper) to Terminal 
"9" (on the drive's TB1), which is factory set for N.O. Start ("0010"), and to either common Terminal "4" or "11"(on the drive's TB1). 
 
 

 

3.4 SCALE TRIMPOT 

If the input Signal is higher than 5 Volts DC, use the SCALE Trimpot to attenuate it. Apply the maximum signal input and set the drive for full 
speed output and observe the display. Rotate the SCALE Trimpot counter clockwise until the drive output frequency begins to drop. Then, 
rotate the SCALE Trimpot clockwise until the display returns to the maximum output frequency. 
 
Set the signal Slope and Type and adjust the Gain, Offset, and Response Time as desired. See Section 8.4.2.1, on page 30 of the manual. 
 
 
 

4 DIAGNOSTIC LEDs 

The two LEDs provide indication of operational status of the IODF. See Figure 1, on page 1, for the location of the PWR (Power On) and ST 
(Status) LEDs. 
 

PWR (Power On) LED:

 When power is applied to the drive, the PWR LED will illuminate green. 

 

ST (Status) LED:

 During normal operation, the ST LED is not illuminated. If the IODF experiences a communication error, the ST LED will 

flash red. If the ST LED flashes, disconnect power to the drive and recheck that the IODF is properly installed. If, after checking the installation 
of the IODF, the ST LED flashes again, contact our Sales Department. 
 
 
 

5 INSTALLING THE NEW COVER 

After installing and wiring the IODF, it is necessary to install the new cover (supplied). For Case A drives, use the small cover and for Case B 
drives, use the large cover. Insert the cover's tab into the slot on the drive and then gently press down on the cover until it snaps into place 
and is secured onto the drive. 
 
 
 
 
 

END OF INSTALLATION INSTRUCTIONS 

Summary of Contents for 9646

Page 1: ...he responsibility of the equipment manufacturer and individual installer to supply this Safety Warning to the ultimate end user of this product SW 8 2012 The drive contains electronic Start Stop circuits which can be used to start and stop the drive However these circuits are never to be used as safety disconnects since they are not fail safe Use only the AC Line for this purpose Be sure to read a...

Page 2: ...ore using the drive Disconnect the main power before making connections to the drive or the IODF To avoid electric shock be sure to properly ground the drive Application Note To avoid erratic operation do not bundle AC Line input and motor wires with each other Also do not bundle motor wires from multiple drives in the same conduit Use shielded cables on all signal wiring over 12 30 cm The shield ...

Page 3: ... 14 13 15 17 19 18 19 Common 1 N O Normally Open COM Relay Common 2 TB3 on IODF N C Normally Closed Run Fault Target Frequency 5 03 5 04 Frequency Threshold Level 5 03 5 04 Frequency Threshold Level 5 03 5 04 I 2 t or I t Fault Load Loss See 5 05 External Fault Notes 1 Common Terminals 16 and 19 are internally wired together These terminals are also internally wired to Terminals 4 and 11 on the dr...

Page 4: ...peed output and observe the display Rotate the SCALE Trimpot counter clockwise until the drive output frequency begins to drop Then rotate the SCALE Trimpot clockwise until the display returns to the maximum output frequency Set the signal Slope and Type and adjust the Gain Offset and Response Time as desired See Section 8 4 2 1 on page 30 of the manual 4 DIAGNOSTIC LEDs The two LEDs provide indic...