Kaysun KWF-140 HT ACS Owner'S Manual Download Page 26

04:27

27-05-2019

sun

OK

CONFIRM

HB01#   E1

Communication fault between controller and hydro 

box.

Please contact your dealer.

SERVICE INFORMATION

PARAMETER

ROOM SET TEMP.

MAIN SET TEMP

TANK SET TEMP.

ROOM ACTUAL TEMP.

-°C

45°C

40°C

-°C

SERVICE

CALL

ERROR

CODE

DISPLAY

SCROLL

1/2

SERVICE INFORMATION

PARAMETER

TIME

DATE

LANGUAGE

BACKLIGHT

18:39

03-06-2019

EN

ON

SERVICE

CALL

ERROR

CODE

DISPLAY

SCROLL

1/2

SERVICE INFORMATION

PARAMETER

MAIN ACTUAL TEMP.

TANK ACTUAL TEMP.

25°C

25°C

SERVICE

CALL

ERROR

CODE

DISPLAY

SCROLL

2/2

SERVICE INFORMATION

PARAMETER

SCREEN LOCK TIME

ON

300 SEC

SERVICE

CALL

ERROR

CODE

DISPLAY

2/2

SCROLL

ON/OFF

ON/OFF

BUZZER

OPERATION PARAMETERS

HYDRO BOX

OUTDOOR UNITS

OK

ENTER

SCROLL

SCROLL

1/6

OFF

0.0 A

0 HZ

1    MIN

95    MIN

3    MIN

OPERATION PARAMETERS

OPERATION MODE

COMPRESSOR FREQUENCY
COMP. RUN TIME 1
COMP. RUN TIME 2

COMP. RUN TIME 3 

CURRENT

SCROLL

2/6

80 Hrs

0    P
0    P

25°C
25°C
25°C

OPERATION PARAMETERS

COMP. RUN TIME 4

EXPANSION VALVE 2
TWOUT
TWIN

TTANK

EXPANSION VALVE 1

24

Press OK to show the mean of the error code:

NOTE:
A total of twenty fault codes can be recorded.
The parameter function is used to display the main 

parameter, and there are two pages to show the 

parameter:

The DISPLAY function is used to set the interface:

Use ''OK'' to enter and use ''◄

'', ''

►▼'', ''▲'' to scroll.

6.7 OPERATION PARAMETERS

Spot check the operating parameters of the hydro 

module and some operating parameters of the ODU. 
This menu is for installer or service engineer reviewing 

the operation parameter of hydro box and ODU units.

 

● At the home page, go to ''MENU'' > ''OPERATION 

PARAMETERS''. 

 

● Press ''OK''. There are six pages for the operating 

parameter as following. Use ''▼'', ''▲'' to scroll.

The parameters of hydro box are as follows:

Summary of Contents for KWF-140 HT ACS

Page 1: ...r Before using your air conditioner please read this manual carefully and keep it for future reference The figure shown in this manual is for reference only and may be slightly different from the actu...

Page 2: ...8 5 BASIC APPLICATION 5 1 Unlocking the Screen 08 5 2 Enabling Disabling Mode and Setting Temperature 09 6 FUNCTIONS 6 1 HEAT MODE 12 6 2 DOMESTIC HOT WATER DHW 15 6 3 SCHEDULE Function 17 6 4 OPTIONS...

Page 3: ...e been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children must be supervised to ensure that they do not play with the product Unit are m...

Page 4: ...45 04 27 MAIN ROOM Preset temp is unchanged Preset temp decreases Preset temp increases 27 05 2019 The anti freezing protection function has been enabled C C The heat recovery function has been enabl...

Page 5: ...eat mode is classified into leaving water temperature control FOR SERVICEMAN Heat mode setting LEAVING WATER TEMP YES and room temperature control FOR SERVICEMAN Heat mode setting ROOM TEMP YES The le...

Page 6: ...3 14 15 16 17 8 10 9 2 3 11 4 1 6 6 5 7 04 27 sun DHW TANK ON 45 C 04 Scenario 2 Only heat mode is available and the hydro module operates in room temperature control mode For more information please...

Page 7: ...45 C 45 C Sets the desired water tank temperature ranging from 25 C to 80 C Sets the desired leaving water temperature ranging from 25 C to 80 C Indicates leaving water temperature control 05 Scenario...

Page 8: ...on please read the Installation Manual and see Multiple Set Points on Page 14 in this document The settings of multiple set points do not affect the main interface The temperature of multiple set poin...

Page 9: ...er query 5 The circulating pump and water tank temperature sensor should be connected to the master hydromodule To enable the group control function you need to set the DIP switch on the main board as...

Page 10: ...nterface press MENU The following interface is displayed 5 BASIC APPLICATION 5 1 Unlocking the Screen If you do not operate the wired controller for a long time by default 120s which can be set on the...

Page 11: ...nd disabled through the wired controller 5 2 1 Heat Mode There are two control methods for the heat mode Leaving water temperature control Room temperature control Leaving water temperature control In...

Page 12: ...ually or through the timer function and weather temperature curve Take the following steps to set room temperature control mode MENU FOR SERVICEMAN HEAT MODE ROOM TEMP Set ROOM TEMP to YES Room temper...

Page 13: ...7 27 05 2019 sun OK CONFIRM NO YES SCROLL DHW mode ON OFF function is locked Do you want to unlock it 11 5 2 2 DHW Mode Take the following steps to set the DHW mode MENU FOR SERVICEMAN DHW MODE Set DH...

Page 14: ...TURE The PRESET TEMP function will be automatically disabled in the following conditions 1 Timer is set 2 Weekly schedule is set Take the following steps to enable PRESET TEMP MENU PRESET TEMPERATURE...

Page 15: ...water outlet temperature control of heat mode If ROOM TEMP is set to YES on the wired controller the following information is displayed 6 1 2 WEATHER TEMP SET WEATHER TEMP SET WEATHER TEMPERATURE On...

Page 16: ...mbient temperature H_weather_Twout the desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature indicates the desired water outlet temperature...

Page 17: ...required water temperature of multiple set point 2 4 The energy demand of space 1 is determined according to the thermostat 1 If thermostat 1 is on it indicates that there is an energy demand while i...

Page 18: ...UNNING TIME is 30 minutes Set as follows Notes 1 If DHW MODE NON choose MENU DOMESTIC HOT WATER Press OK The following interface is displayed 2 If DISINFECT MODE NON on the FOR SERVICEMAN interface ch...

Page 19: ...weekly schedule function is enabled the timer function will be disabled Use to scroll and use to adjust the time the mode and the temperature Move to press OK to select or unselect the timer is selec...

Page 20: ...LE Timer and weekly schedule cannot take effect at the same time The time which is set later will take effect first If the weekly schedule is set the icon will be displayed on the main interface Choos...

Page 21: ...ON ON 45 45 C C 19 6 3 4 CANCEL TIMER Go to MENU SCHEDULE CANCEL TIMER Press OK The following page will appear Use to move to YES Press OK to cancel the timer If you want to exit CANCEL TIMER press BA...

Page 22: ...grade the capability of the hydro module You can set the hydro module to always operate in silent mode or to enter silent mode within a period of time On the main interface you can check whether silen...

Page 23: ...e set disinfection time prior to the end of the holiday For example if FROM 2020 01 02 UNTIL 2020 01 16 and disinfection time is set to 23 00 on Friday disinfection begins from 23 00 on 2020 01 10 If...

Page 24: ...cording to the schedule settings of the holiday mode without affecting the normal schedule If the holiday home mode is activated will display on the home page Go to MENU OPTIONS HOLIDAY HOME Press OK...

Page 25: ...1 5 HB01 E1 17 32 03 06 2019 23 Use and to scroll and ON OFF to select LOCK or UNLOCK The heat DHW temperature can t be adjusted when the HEAT TEMP ADJUST DHW TEMP ADJUST is locked If you want to adj...

Page 26: ...PERATION PARAMETERS OPERATION MODE COMPRESSOR FREQUENCY COMP RUN TIME 1 COMP RUN TIME 2 COMP RUN TIME 3 CURRENT SCROLL 2 6 80 Hrs 0 P 0 P 25 C 25 C 25 C OPERATION PARAMETERS COMP RUN TIME 4 EXPANSION...

Page 27: ...V01 OPERATION PARAMETERS HYDRO BOX SOFTWARE CONTROLLER SOFTWARE OPERATION PARAMETERS HYDRO BOX OUTDOOR UNITS OK ENTER SCROLL SCROLL 1 3 0 HZ 0 kPa 0 kPa 0 C 25 C V01 OPERATION PARAMETERS ODU1_INV ODU1...

Page 28: ...temperature TCS Desired discharge pipe pressure saturation temperature PC Discharge pipe pressure PE Suction pipe pressure TC Discharge pipe pressure saturation temperature TE Scution pipe pressure sa...

Page 29: ...0 23 50 1 10 h min Temper 3 PRESET TEMP 3 45 25 80 1 C PRESET TEMP TIMER4 PRESET TEMP timer 3 on off 0 Off 1 On 0 0 1 1 PRESET TEMP TIME4 PRESET TEMP time 4 0 00 0 00 23 50 1 10 h min Temper 4 PRESET...

Page 30: ...0 1 10 h min SILENT MODE TIMER ENDT 2 Silent mode timer end time 2 7 00 0 00 23 50 1 10 h min HOLIDAY AWAY CURRENT STATE Holiday away mode on off 0 Off 1 On 0 0 1 1 HOLIDAY AWAY DHW MODE Holiday away...

Page 31: ...r hydro module operation is 16 A Speed 1 It indicates that the maximum current for hydro module operation is 15 A Speed 2 It indicates that the maximum current for hydro module operation is 14 A Speed...

Page 32: ...l Ta 2 1 10 1 C WEATHER TEMP SETTING L_weather_Twout Water outlet temperature at low air temperature 70 25 80 1 C H_weather_Twout Water outlet temperature at high air temperature 45 25 80 1 C L_ODU_T4...

Page 33: ...ry setting 8 Test run 9 Heat recovery mode setting 10 Power input limitation 11 SMART GRID 12 Hydro box addressing 1 DHW MODE 2 Disinfect mode 3 DHW priority 4 dTtankSH 5 TtankS_DI 6 t_DI_HIGHTEMP 7 t...

Page 34: ...ove the electric heater from the sanitary hot water tank and immerse in a bucket or similar with lime removing product for 24 hours Indoor unit control box 1 Carry out a through visual inspection of t...

Page 35: ...ature sensor error FA Suction pipe temperature sensor error F7 IDU same address error FC R410a loop liquid pipe temperature sensor error Fd R134a loop liquid pipe temperature sensor error F8 Room temp...

Page 36: ...16123000001852 V A...

Page 37: ......

Page 38: ......

Reviews: