OWNER’ S MANUAL

CENTRAL MONITOR CONTROL

 

KMC-32 E

Thank you very much for purchasing our product. 

Before using your unit, please read this manual carefully and keep it for future 

reference. 

Summary of Contents for KMC-32 E

Page 1: ...1 OWNER S MANUAL CENTRAL MONITOR CONTROL KMC 32 E Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference ...

Page 2: ...ecautions that should be brought to your attention during operation In order to ensure correct service of the wired controller please read this manual carefully before using the unit For convenience of future reference keep this manual after reading it ...

Page 3: ...3 CONTENTS 1 SAFETY PRECAUTION 1 2 SUMMARIZE OF OUTDOOR KMC 2 3 BASIC REQUIREMENTS 3 4 OPERATION 3 5 INSTALLATION 10 6 TECHNICAL INDEX AND REQUIREMENT 11 ...

Page 4: ...ion Identifier Meaning Warning Means improper handling may lead to personal or severe injury Caution Means improper handling may lead to personal injury or property loss Note 1 Harm means injury burn and electric shock which need long term treatment but need no hospitalization 2 Property loss means loss of properties and materials lcon Meaning It indicates forbidding The forbidden subject matter i...

Page 5: ...s only can be realized when the system is in normal operation 1 Central Control Monitor can realize the central control and data query to outdoor units One outdoor KMC can connect max 8 refrigerant system by NIM so each outdoor KMC can connect max 8 systems are multiplied by max 4 sets outdoor units per system equals max 32 outdoor units And it adopts wire connecting method communication to realiz...

Page 6: ...be off 2 second later the system enters into normal display state the KMC is in the main page and display the data in the first page Network Area Address Setting The PC or gateway can connect max 16 sets KMC Every KMC can be viewed as one network area and be distinguished by address set through the address setting button in keyboard The setting range is 16 31 Address setting method pressing the Ad...

Page 7: ... BUTTON Push it to enter into the query state 2 PREVIOUS BUTTON On the query state push it to query in default the running states of other online air conditioners 3 NEXT BUTTON On the query state push it to query in default the running states of other online air conditioners QUERY SET MODE PREVIOUS PAGE UP NEXT PAGE DOWN ADDRESS Graph 1 Button Distribution on KMC LOCK OK M ...

Page 8: ...n to enter into Set Page 7 MODE BUTTON Pressing MODE button to enter into MODE set and select circularly between Forced Cooling and OFF state 8 OK BUTTON Pressing OK button to confirm all settings and send to the corresponding air conditioners 9 LOCK BUTTON All the other button will not be on controlled anytime when pushing the button and unlock happens when push it again 10 ADDRESS SET BUTTON In ...

Page 9: ...nication connection with outdoor unit and it will be off in 20 seconds with communication 4 Press the OK button in setting page and waiting for 4 seconds success or fail will be shown in the operation state area Stand by Page Display 1 Figure means the total number of online modules 2 Figure means the total number of online outdoor units 4 2 2 Datas Graph 2 LCD Screen OR display with the model MD ...

Page 10: ...tate Display COMP 1 2 3 4 6 Electromagnetism Valve Display EMV 1 2 3 4 5 6 7 4 Ways Valve Display 8 Defrost Display Defrost 9 Oil Return Display OIL RETURN 10 Page0 displays the consumption of electric energy with ELECTRIC ENERGY Kwh and the number 11 Page1 displays the input power frequency with Frequency Hz and the number 12 Page2 displays the total number of indoor units 13 Page3 displays the t...

Page 11: ... Page14 displays the openness of electromagnetism valve symboled 2 with VALVE OPENNESS 2 and the number 25 Page15 displays the most advanced malfunction with MALFUNCTION and the code 26 Page16 displays the most advanced protection with PROTECTION and the code The page will increase or decrease by 1 every time you press PAGE UP or PAGE DOWN Select the online outdoor unit by push the previous or nex...

Page 12: ...ion valid for host unit P8 Compressor Current 3rd Protection H1 Net communication malfunction P7 Compressor Current 2nd Protection EF Other malfunction P5 Condenser High Temp Protection E4T4 Temp Sensor malfunction P4 Discharge Pipe Temp Protection E3T3 Temp Sensor malfunction P3 Compressor Current 1st Protection E2 Sensor malfunction P2 Discharge Low pressure Protection E1 Phase sequence or lack ...

Page 13: ...he concave on bottom panel of the Wire Controller to remove the Back Cover When installing the Wire Controller you should adjust the bottom of the Wire Controller Board to the Wire Controller Back Cover which should be fixed first then press the other end of the Wire Controller Board When installing the Wire Controller Cover be sure there is a hole in the wall to avoid the Wire Controller Back Cov...

Page 14: ...11 6 TECHNICAL INDEX AND REQUIREMENT EMC and EMI should conform to the requirement of CE Certification ...

Page 15: ...12 Version MDV06U 001IW 202000170150 ...