Page 39
Wiring
1) The output of the mainboard engineering
load control interface is a strong electric
signal, so it must be powered off.
2) The engineering load control interface is only
used as a signal output. The total output
current of the mainboard cannot exceed
2.5A, otherwise it will cause overload and
damage the machine.
3) Please connect the engineering load in strict
accordance with the wiring diagram. The
excessive load power needs to be controlled
by the AC contactor. AHS and K_heater2
must pass the AC CONTACTOR control.
4) The connection and installation of external
engineering loads must be well protected,
such as earthed effectively, air switch and
residual current operated circuit-breakers.
The installation of engineering load shall be
installed in strict accordance with the
instruction manual of the load and control
components and local regulations.
"CN400" terminal is used for remote ON-OFF
switch; when using this function, this interface
is connected to external control switch,
remove the short connector of JR400 when
you use the "ON-OFF" function.
The control logic is as follows:
Remote switch short circuit: the machine is
controlled as normal.
Remote switch off: the machine enters remote
control.
3. Remote switch function
4. DIP SWITCH FUNCTION
5. Battery installation
1. The battery is placed in the accessory bag and
needs to be installed in the wired controller on
site.
2. Please remove the wired controller, place the
battery in the unit and ensure the positive side
of the battery is in accordance with the polarity
markings.
3. Set the correct time before operating. Battery
in the wired controller can maintain the correct
time during a power failure. When the power is
restored and the displayed time is not correct,
replace the battery.
Engineering load control interface
2-WAY VALVE
CODE
PART NAME
SV2
Sv3_1,SV3_2 3-WAY VALVE
AHS
CONTROL SIGNAL OF ASSISTANT
HEAT SOURCE
Pumpo
PUMP
PumpT
PUMP FOR RETURN WATER/PUMP
FOR MIXING WATER
K_heater2
CONTROL SIGNAL OF WATER
TANK HEATER
RY2,RY4
RELAY
DIP SWITCH
SW1
TW1B
ON
FUNCTION
DEFAULT SETTING
OFF
SW1-1
ON
1 2 3 4
SW1
SW1-3
SW1-2
SW1-4
OFF
OFF
OFF
OFF
TH
TK
WITHOUT
TW1B
WITH
TW1B
WITHOUT
TH
WITH
TH
WITHOUT
TK
WITH
TK
Note:Slide the switch
to numbers position
indicates OFF .
"
"