28
8.5.2 Connection mode of pipe
The water inlet and outlet pipes are installed and connected as shown in the following figures. KEM-30 DRS4.1 KH model
uses screwed connection, while the KEM-60 DRS4.1 KH,KEM-90 DRS4 KH model uses hoop connection. For the specifications
of the water pipes and screw thread, see the Table 8-7 below.
Table 8-5
Model
Pipe connection methods
Specifications of water pipe
Specifications of screw thread
KEM-30 DRS4.1
KH
Screwed connection
DN40
Rc 1 1/4
KEM-60 DRS4.1
KH
Hoop connection
DN50
/
KEM-90 DRS4 KH
Hoop connection
DN50
/
Fig.8-23 connection mode of KEM-30 DRS4.1 KH
Fig.8-24 connection mode of KEM-60 DRS4.1 KH
Fig.8-25 connection mode of KEM-90 DRS4 KH pipe
8.5.3 Design of the store tank in the system
kW is the unit for cooling capacity and L is the unit for G, water flow in the formula counting the minimum water flow.
Comfortable air conditioner
G= cooling capacity×3.5L
Process cooling
G= cooling capacity×7.4L
In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement, it’s
necessary to mount a tank equipping with a cut-off baffle at the system to avoid water short-circuit, Please see the following