Kaysun KCCHT-04 Owner'S Manual Download Page 15

10

Press the “▼” and “▲” buttons to select the 

module address to view (the offline ad-

dress is skipped automatically), and press 

the “OK” button to enter the interface. The 

screen display is as follows:

Press the “BACK” button to cancel the 

setting and return to the previous interface. 

After the manual defrost is selected and 

opened, “  “ on the main interface is on.

•  Silent setting:

Select “SILENT SETTING”, and press the 

“OK” button to enter the interface. The inter-

face display is as follows:

Press the “▼” and “▲” buttons to select the 

option to enter, and press the “OK” button to 

enter the interface; or press the “BACK”

button to go back to the previous menu. 

Press the “▼” and “▲” buttons to select the

 

a. Setting the standard mode:

Select “STANDARD MENU”, and press the 

“OK” button to enter the interface. The inter-

face display is as follows:

Press the “▼” and “▲” buttons to select the 

desired option, and press the “OK” button to 

save the setting and go back to the previous 

interface. Press the “BACK” button to can-

cel the setting and return to the previous 

interface.

b. Setting the silent mode:

Select “SILENT MENU”, and press the “OK” 

button to enter the interface. The interface 

display is as follows:

Press the “▼” and “▲” buttons to select the

desired option, and press the “OK” button to 

save the setting and go back to the previous 

interface. Press the “BACK” button to can-

cel the setting and return to the previous 

interface.

c. 

Setting the night silent mode (factory 

default setting):

Select “NIGHT SILENT MENU”, and press 

the “OK” button to enter the interface. The 

interface display is as follows:

Summary of Contents for KCCHT-04

Page 1: ...rol KCCHT 04 Original instructions Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference OWNER S MANUAL ...

Page 2: ......

Page 3: ...e precautions that should be brought to your attention during operation To ensure correct service of the wire controller please read this manual carefully before using the unit For convenience of future reference keep this manual after reading it ...

Page 4: ......

Page 5: ...Contents 1 Safety Precautions 1 2 Overview of Wired Controller 2 3 Menu Operations 4 ...

Page 6: ...ges Warning Means improper handling may lead to serious injuries After the installation work is completed confirm that the trial operation is normal and hand over the manual to the customer for keeping Note So called injuries mean the harms not requiring hospitalization or long term treatment generally referring to wounds burns or electric shocks Material damages refer to property and material los...

Page 7: ...ursor on the display navigate in the menu structure adjust the settings Come back to the up level Turn on or off the space operation mode Long press for unlocking locking the controller Go to the next step when programming a schedule in the menu structure confirm a selection enter a submenu in ...

Page 8: ...Number of parallel units Compressor operating Fan on Water pump on External elec tric heater on Set temperature Number of parallel units Timer icon Alarm icon Lock icon Silent mode on Centralized control access of network Anti freezing or manual defrost on ...

Page 9: ...nit is off press ON OFF to power on the unit The mode can be switched under the power off mode only 3 3 Setting Mode In Unlock mode press the MENU bu tton to enter the menu setting interface press the and buttons to select MODE and set a mode and press the OK button as shown in the above figu re to access the submenu mode setting As shown below Three modes available a Cooling mode b Heating mode c...

Page 10: ...s BACK to go back to the previous interface during opera tion on the menu page press BACK to go back to the previous interface After entry the interface is displayed as follows State query Select STATE QUERY and press the OK button to enter the interface The inter face display is as follows Current error Select CURRENT ERROR and press the OK button to enter the interface The inter face display is ...

Page 11: ...cross with that of Time1 For example if Timer1 ON is set to 12 00 for Timer1 and Timer1 OFF is set to 15 00 then the values of Timer2 ON and Time2 OFF can be accessed in the range of 12 00 15 00 If timing intervals cross each other the timed on signal is sent in the case of Timer ON and the timed off signal is sent in the case of Timer OFF After timer setting is completed the corresponding prompt ...

Page 12: ...is as follows Press the and buttons to select the date time and time format to be set and press the OK button to access the lower layer submenu Operation instructions Press the and buttons to select year month and date press the and buttons to adjust the parameter value and press the OK button to save the set ting Time setting operation instructions Press the and buttons to select hour and minute ...

Page 13: ...ed After entering the password press the OK button to enter the interface press the BACK button to go back to the previous interface the display is as follows if the input is incorrect The query interface as follows is displayed if the input is correct State query Select STATE QUERY and press the OK button to enter the interface The screen prompts the user to select the ad dress for query as shown...

Page 14: ...o view the offline ad dress is skipped automatically and press the OK button to enter the interface The screen display is as follows Press the BACK button to go back to the previous interface the system returns to the main page if there is no operation in 60s Manual defrost Select MANUAL DEFROST and press the OK button to enter the interface The screen prompts the user to select the ad dress for q...

Page 15: ...he a Setting the standard mode Select STANDARD MENU and press the OK button to enter the interface The inter face display is as follows Press the and buttons to select the desired option and press the OK button to save the setting and go back to the previous interface Press the BACK button to can cel the setting and return to the previous interface b Setting the silent mode Select SILENT MENU and ...

Page 16: ...revious interface Press the BACK button to can cel the setting and return to the previous interface Querying history error Select HISTORY ERROR and press the OK button to enter the interface The screen prompts the user to select the ad dress for query as shown below Press the and buttons to select the module address to view the offline address is skipped automatically and press the OK button to en...

Page 17: ...e The screen prompts the user to enter the password as shown below The initial password is 9999 and cannot be changed Press the and buttons to change the number to enter and press the and buttons to change the bit code to enter After the number is entered the display is not changed After entering the password press the OK button to enter the interface press the BACK button to go back to the previo...

Page 18: ... the OK button to enter the interface The inter face display is as follows Press the and buttons to adjust the parameter and press the OK button to save the setting and return to the previous interface Press the BACK button to can cel the setting and return to the previous interface c Exit defrost temperature Select EXIT DEFROST TEMP and press the OK button to enter the interface The interface dis...

Page 19: ...he interface display is as follows Press the and buttons to adjust the parameter and press the OK button to save the setting and return to the previous interface Press the BACK button to can cel the setting and return to the previous interface g Anti freezing temperature of normal tem perature outlet water Select ANTI FREEZING TEMP OF NOR MAL TEMP OUTLET WATER and press the OK button to enter the ...

Page 20: ...for the first time for heating Select OPEN THE FRIST HEATING UNIT SET PROPORTION and press the OK button to enter the interface The interface display is as follows k Delay off time for water pump Select DELAY OFF TIME FOR WATER PUMP and press the OK button to enter the interface The interface display is as follows Press the and buttons to adjust the parameter and press the OK button to save the se...

Page 21: ...the OK button to enter the interface The inter face display is as follows Press the and buttons to adjust the parameter and press the OK button to save the setting and return to the previous interface Press the BACK button to can cel the setting and return to the previous interface 3 7 Setting MENU Press the MENU button to enter the query interface below The user first uses the and buttons to sele...

Page 22: ...wer on off status mode set temperature failure protection wired controller address timer hysteresis etc However the memori zed content must be the content set at least 7s before the power failure 3 10 Parallel Function of Wired Controller 1 A maximum of 16 wired controllers can be connected in parallel and the ad dress can be set in the range of 0 to 15 2 After wired controllers are connec ted in ...

Page 23: ...ng operation 6 After any of parallel wired controllers has been reset the address of this wired controller is 0 by default 3 11 Upper Computer Commu nication Function Reserved 1 The home page displays the content below during communication with the upper computer Communication between the wired controller and the upper computer 2 If the outdoor main control board is in the remote ON OFF control mo...

Page 24: ...hock or fire Strictly follow this manual Improper installation may lead to electric shock or fire Reinstallation must be performed by professionals improper installation may lead to electric shock or fire Do not disassemble your air conditioner at will A random disassembly may cause abnormal operation or heating which may result in fire Do not install the unit in a place vulnerable to leakage of f...

Page 25: ...he electric cabinet 6 Plastic expansion pipe 3 For Mounting on the Wall 6 2 3 Note to installation of wire controller 1 This installation manual contains information about the procedure of installing Wired Remote Controller Please refer to Indoor Unit Installation Manual for connecting between Wired Remote Controller and Indoor Unit 2 Circuit of Wired Remote Controller is low voltage circuit Never...

Page 26: ...21 6 3 Installation procedure and matching setting of wire controller 6 3 1 Structure size figure ...

Page 27: ...22 6 3 2 Wiring Input Voltage A B 13 5VAC Wiring size 0 75mm2 Main Unit control box Wire controller ...

Page 28: ...k cover Front cover Straight head screwdriver Screw hole installed on the wall use three GB950 86 M4X20 Screw hole fixed on the wall use one GB950 86 M4X20 Screw hole installed on 86 Electrician box use two M4X25 GB823 88 Back cover Signal swit ching wires ...

Page 29: ... for fixing on the wall 4 Adjust the length of two plastic screw bars in the accessory to be standard length from the electrical box screw bar to the wall Make sure when install the screw bar to the wall make it as flat as the wall 5 Use cross head screws to fix the wire controller bottom cover in the wall through the screw bar Make sure the wire controller bottom cover is on the same level after ...

Page 30: ...ll hole and wiring hole Dia meter Φ8 Φ10 Electrician box Putty Putty Putty Trap Trap Trap Avoid the water enter into the wired remote controller use trap and putty to seal the connectors of wires du ring wiring installation ...

Page 31: ...r and then buckle the front cover avoid clamping the commu nication switching wire during installation Correct install the back cover and firmly buckle the front cover and back cover otherwise will make the front cover drop off Sensor can not be affected with damp ...

Page 32: ...r anti freezing temperature sensor T62 error 10 EC Wired controller detected that the units on line reduction 11 1Ed System A discharge pipe temperature sensor error 2Ed System B discharge pipe temperature sensor error 12 EF Inlet water temperature sensor error 13 EH System self check error alarm 14 EP Discharge pipe temperature sensor error alarm 15 EU Total cooling outlet temperature sensor Tz e...

Page 33: ... protection in heating mode 28 PL Tfin module high temperature protection Pro tection occurs for 3 times in 100 minutes and the failure can be recovered by power discon nection only 29 1PU DC fan A module protection 2PU DC fan B module protection 30 1H0 System A IPM module Communication error 2H0 System B IPM module Communication error 31 H1 Under Over voltage protection 32 1H4 Three times 1PP pro...

Page 34: ...4 MCE error 43 L5 Zero speed protection 44 L7 Phase sequence error 45 L8 Compressor frequency variation greater than 15Hz within one second protection 46 L9 Actual compressor frequency differs from tar get frequency by more than 15Hz protection 47 dF Defrosting prompt ...

Page 35: ...MD16IU 014AW 16117100001020 ...

Page 36: ......