2. INSTALLATION ACCESSORY
Precaution of install the wire controller
1. This manual provides the installation method of wire controller. Please refer to the wiring
diagram of this installation manual to wire the wire controller with indoor unit
2. The wire controller working in low voltage loop circuit. Forbid to directly contact the
cable of 220Vcommercial electricity or of 380V high voltage, and don’t wire this kind of
wire in the said loop; wiring clearance between congured tubes should at the range of
300~500mm or above.
3. The Shielded wire of the wire controller must be grounded reliable.
4. Upon nish the wire controller connection, do not employed tramegger to detect the insu-
lation.