If you will install the unit on the ground or on a 

concrete mounting platform, do the following:

1.  Mark the positions for four expansion bolts based on 

dimensions chart.

2.  Pre-drill holes for expansion bolts.
3.  Place a nut on the end of each expansion bolt.
4.  Hammer expansion bolts into the pre-drilled holes.
5.  Remove the nuts from expansion bolts, and place 

outdoor unit on bolts.

6.  Put washer on each expansion bolt, then replace the 

nuts.

7.  Using a wrench, tighten each nut until snug.

WARNING

WHEN DRILLING INTO CONCRETE, EYE PROTECTION 

IS RECOMMENDED AT ALL TIMES.
If you will install the unit on a wall-mounted bracket, 

do the following:

CAUTION

Make sure that the wall is made of solid brick, concrete, 

or of similarly strong material.

 The wall must be able to 

support at least four times the weight of the unit.

1.  Mark the position of bracket holes based on 

dimensions chart.

2.  Pre-drill the holes for the expansion bolts.
3.  Place a washer and nut on the end of each expansion 

bolt.

4.  Thread expansion bolts through holes in mounting 

brackets, put mounting brackets in position, and 

hammer expansion bolts into the wall.

5.  Check that the mounting brackets are level.
6.  Carefully lift unit and place its mounting feet on 

brackets.

7. 

Bolt the unit firmly to the brackets.

8.  If allowed, install the unit with rubber gaskets to 

reduce vibrations and noise.

Step 4: Connect signal and power cables

The outside unit's terminal block is protected by 

an electrical wiring cover on the side of the unit. A 

comprehensive wiring diagram is printed on the inside of 

the wiring cover.

WARNING

BEFORE PERFORMING ANY ELECTRICAL OR 

WIRING WORK, TURN OFF THE MAIN POWER TO 

THE SYSTEM.

1.  Prepare the cable for connection:

USE THE RIGHT CABLE

•  Indoor Power Cable (if applicable): H05VV-F or 

H05V2V2-F

•  Outdoor Power Cable: H07RN-F

•  Signal Cable: H07RN-FF

CHOOSE THE RIGHT CABLE SIZE

The size of the power supply cable, signal cable, fuse, 

and switch needed is determined by the maximum current 

of the unit. The maximum current is indicated on the 

nameplate located on the side panel of the unit. Refer to 

this nameplate to choose the right cable, fuse, or switch.

a.  Using wire strippers, strip the rubber jacket from 

both ends of cable to reveal about 40mm (1.57in) of 

the wires inside.
b.  Strip the insulation from the ends of the wires.
c.  Using a wire crimper, crimp u-lugs on the ends of 

the wires.

PAY ATTENTION TO LIVE WIRE

While crimping wires, make sure you clearly distinguish 

the Live ("L") Wire from other wires.

WARNING

ALL WIRING WORK MUST BE PERFORMED 

STRICTLY IN ACCORDANCE WTH THE WIRING 

DIAGRAM LOCATED INSIDE OF WIRE COVER OF 

THE OUTDOOR UNIT.

2.  Unscrew the electrical wiring cover and remove it.
3.  Unscrew the cable clamp below the terminal block 

and place it to the side.

4.  Connect the wire according to the wiring diagram, and 

firmly screw the u-lug of each wire to its corresponding 

terminal.

5.  After checking to make sure every connection is 

secure, loop the wires around to prevent rain water 

from flowing into the terminal.

6.  Using the cable clamp, fasten the cable to the unit. 

Screw the cable clampd down tightly.

7.  Insulare unused wires with PCV electrical tape. 

Arrange them so that they do not touch any electrical 

or metal parts.

8.  Replace the wire cover on the side of the unit, and 

screw it in place.

Summary of Contents for CASUAL Series

Page 1: ...applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product Fiche in the packaging of the outdoor unit KAY CF 26 DR9 KAY CF 35 DR9 KAY CF 52 DR8 KAY CF 7...

Page 2: ...ns 4 Owner s Manual 1 Unit Specifications and Features 7 1 Indoor unit display 7 2 Operating temperature 8 3 Other features 8 4 Setting angle of airflow 9 5 Manual operation without Remote 10 2 Care a...

Page 3: ...7 Wrap piping and cables 22 8 Mount indoor unit 23 8 Outdoor Unit Installation 24 1 Select installation location 24 2 Install drain joint 24 3 Anchor outdoor unit 25 4 Connect signal and power cables...

Page 4: ...in places near or around combustible gases Emitted gas may collect around the unit and cause explosion Do not operate your air conditioner in a wet room such as a bathroom or laundry room Too much ex...

Page 5: ...E NOTE OF FUSE SPECIFICATIONS The air conditioner s circuit board PCB is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such as...

Page 6: ...aging of the outdoor unit 2 Installation service maintenance and repair of this unit must be performed by a certified technician 3 Product uninstallation and recycling must be performed by a certified...

Page 7: ...R ON is set FRESH SWING TURBO or SILENCE feature is turned on OF for 3 seconds when TIMER OFF is set FRESH SWING TURBO or SILENCE feature is turned off cF when anti cold air feature is turned on dF wh...

Page 8: ...low 0 C 32 F we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance NOTE Room relative humidity less than 80 If the air conditioner operates in excess of th...

Page 9: ...ill increase the temperature by 1 C 2 F after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by 1 C 2 F after 1 hour and wil...

Page 10: ...To restore regular operation use the remote control to activate the unit Unit must be turned off before manual To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side o...

Page 11: ...r Air Filter A clogged air conditioner can reduce the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of t...

Page 12: ...isplay To reset the reminder press the LED button on your remote control 4 times or press the MANUAL CONTROL button 3 times If you don t reset the reminder the CL indicator will flash again when you r...

Page 13: ...rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the i...

Page 14: ...rvice center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a rep...

Page 15: ...ating performance The voltage is too high or too low Install a manostat to regulate the voltage Cold air entering through doors and windows Make sure that all doors and windows are closed during use C...

Page 16: ...holder optional 1 Mounting plate 1 Fixing screw for remote controller holder optional 2 Anchor 5 8 dependinf on model Small Filter Need to be installed on the back of main air filter by the authorized...

Page 17: ...ation Location Determine Wall Hole Position Attach Mounting Plate Drill Wall Hole Connect Piping Connect Wiring Prepare Drain Hose Wrap Piping and Cable Mount Indoor Unit Page 17 5 Installation Summar...

Page 18: ...ounting Plate 2 Front Panel 3 Power Cable Some Units 4 Louver 5 Functional Filter On Back of Main Filter Some Units 6 Drainage Pipe 7 Signal Cable 8 Refrigerant 9 Remote Controller 10 Remote Controlle...

Page 19: ...cable and refrigerant piping that connect the infoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the unit However the unit can accomodate p...

Page 20: ...t the unit 2 If the wall hole is behind the unit keep the knock out panel in place If the wall hole is to the side of the indoor unit remove the plastic knock out panel from that side of the unit This...

Page 21: ...ower supply stop work immediately Explain your reasoning to the client and refuse to install the unit until the safety issue is properly resolved 4 Power voltage should be within 90 110 of rated volta...

Page 22: ...he unit remove the plastic panel on the bottom left hand side 5 Feed the signal wire through this slot from the back of the unit to the front 6 Facing the front of the unit connect the wire according...

Page 23: ...the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate...

Page 24: ...ion that is exposed to large amounts of dust In a location exposed to a excessive amounts of salty SPECIAL CONSIDERATIONS FOR EXTREME WEATHER If the unit is exposed to heavy wind Install unit so that...

Page 25: ...ation base of the unit according to the dimensions below Outdoor Unit Dimensions mm Mounting Dimensions A x H x F Distance A mm Distance B mm 681 x 434 x 285 26 8 x 17 1 x 11 2 460 18 1 292 11 5 700 x...

Page 26: ...on the inside of the wiring cover WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK TURN OFF THE MAIN POWER TO THE SYSTEM 1 Prepare the cable for connection USE THE RIGHT CABLE Indoor Power Cab...

Page 27: ...frigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the need for future maintenance 1 Measure the distance between the indoor and outdoor u...

Page 28: ...is fully flared 8 Remove the flaring tool and flare form then inspect the end of the pipe for cracks and even flaring Step 4 Connect pipes When connecting refrigerant pipes be careful not to use exce...

Page 29: ...the table above Instructions for Connecting Piping to Outdoor Unit 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared...

Page 30: ...r at least 15 minutes or until the Compound Meter reads 76cmHG 105Pa del sistema 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that t...

Page 31: ...outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Met...

Page 32: ...resistance tester Grounding resistance must be less than 0 1 DURING TEST RUN Check for Electrical Leakage During the Test Run use an electroprobe and multimeter to perform a comprehensive electrical...

Page 33: ...CONNECTIONS During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double ch...

Page 34: ...ange without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the lates...

Page 35: ......

Page 36: ......

Reviews: