Bench Test:

For incoming inspection or failure evaluation, connect the P528 to a dc voltage supply (off).
The voltage supply should be set to 5 volts.
Connect the output leads to a volt meter. With no pressure on the unit, turn on the power supply and read 
the output signal on the volt meter.
The reading should correspond to the specification indicated for null offset. If not, check the connections, 
wire color code and the setting of the power supply.

Electrical Installation and Wiring Guide

Safety Considerations:

Prior to installation and start-up of the P528 Pressure Sensor, you should verify that you have selected the 
appropriate scale range, and that the P500 meets your desired performance and specific measurement 
conditions.

You MUST observe the relevant local/national regulations and observe the applicable standards and  
directives for special applications (e.g. with dangerous media such as acetylene, flammable gasses or 
liquids and toxic gases or liquids and with refrigeration plants or compressors). 

Should you NOT observe 

the appropriate regulations, serious injuries and/or damage can occur!

Open pressure connections only after the system is without pressure!

DO NOT use the P528 outside of the overload threshold. Make sure that the device is used only within the 
overload threshold limit at all times.

Observe the ambient working conditions of the P528.

Only use the P528 with compatible liquids and gases and avoid installing the sensor in an environment 
with mechanical hazards.

Only use the P528 in accordance with the installation guidelines as described within this document: 

Installation Guide – P528 OEM Refrigeration Pressure Sensor

Summary of Contents for P528

Page 1: ...c system application Hydraulic pressure fluctuations can result in very high and very fast peak pressures i e water hammer effect To avoid damaging liquid surges fluid lines should remain full if possible pumps should be brought up to power slowly and valves should be opened slowly To avoid damage from both fluid hammer and surges a surge chamber should be installed If system pressure pulses are a...

Page 2: ...in industrial applications where the process media to be measured is compatible with 304 stainless steel or brass Mechanical Installation A B Electro Magnetic Interference The electronic circuitry of the P528 has been designed to minimize the effect of electromagnetic and radio frequency interference RFI EMI To minimize susceptibility to noise avoid running the termination wiring in a conduit that...

Page 3: ...e selected the appropriate scale range and that the P500 meets your desired performance and specific measurement conditions You MUST observe the relevant local national regulations and observe the applicable standards and directives for special applications e g with dangerous media such as acetylene flammable gasses or liquids and toxic gases or liquids and with refrigeration plants or compressors...

Page 4: ...prevent the sensor from being reinstalled accidentally Should you be required to remove the P528 from service take all necessary precautions with regard to the remaining process media that may still reside within the pressure port as it may be hazardous or toxic Repairs to the P528 should be made by Kavlico only To obtain a Return Material Authorization Number RMA call 619 710 2000 Before removing...

Reviews: